Cabling the Dell™
PowerEdge™ R710
 
A Dell Technical White Paper 
By Chris M. Kitten and Jose L. Flores
Dell │ Datacenter Infrastructure Engineering
March 2009
 
 
 

Advertisement

Table of Contents
loading

Summary of Contents for Dell PowerEdge 2410

  • Page 1           Cabling the Dell™ PowerEdge™ R710   A Dell Technical White Paper  By Chris M. Kitten and Jose L. Flores Dell │ Datacenter Infrastructure Engineering March 2009      ...
  • Page 2 Cabling the Dell™ PowerEdge™ R710                                    THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY CONTAIN TYPOGRAPHICAL ERRORS AND  TECHNICAL INACCURACIES. THE CONTENT IS PROVIDED AS IS, WITHOUT EXPRESS OR IMPLIED WARRANTIES OF  ANY KIND.  © 2009 Dell Inc. All rights reserved. Reproduction of this material in any manner whatsoever without the express  written permission of Dell Inc. is strictly forbidden. For more information, contact Dell.  Dell, the DELL logo, and the DELL badge, PowerEdge, is a trademark of Dell Inc.      Page ii   ...
  • Page 3: Table Of Contents

    Cabling the Dell™ PowerEdge™ R710    Table of Contents     Introduction  ................................  2   Cabling a PowerEdge R710 with CMA ........................  2   2.1  Installing the Cables to the System  .........................  2   Figure 1: System with Cables Installed ......................  2   2.2  Route the Power Cables Through the Strain Reliefs ..................  3   Figure 2:  Routing Power Cables Through the Strain Reliefs .................  3   2.3  Routing the Cables Through the CMA  ......................  3   Figure 3:  Routing the Cables Through the CMA ...................  4   Figure 4: Completed Left Side Mounted CMA Installation ................  5  ...
  • Page 4: Introduction

    Cabling the Dell™ PowerEdge™ R710    Introduction  This white paper describes recommended cable routing procedures, both with and without the optional Cable  Management Arm (CMA) for the Dell™ PowerEdge™ R710 in the following racks:  • PowerEdge 4210  • PowerEdge 2410  • PowerEdge 4220  • PowerEdge 2420  If using the optional CMA, following these procedures will allow you to extend the system from the rack for service  without powering down or disconnecting the cables. If not using the CMA, following these procedures will ensure  secure attachment and strain relief of the cables behind the system. For guidelines on how to route cables within  the rack, refer to the Dell White Paper “Best Practices Guide for Rack Enclosures.”  Cabling a PowerEdge R710 with CMA  This section details how to cable a PowerEdge R710 using a CMA. If you are cabling the system without the  optional CMA, please refer to “Cabling a PowerEdge R710 Without a CMA” later in this white paper.  Follow the instructions contained in the Rack Installation Guide found in the rail kit to install the server into the  rack and to install the cables. All illustrations in the following sections were created using a PowerEdge R710.  NOTE:  The PowerEdge R710 is not compatible with previous‐generation rails and CMAs.  2.1  Installing the Cables to the System  Attach the CMA tray to the back of the rails as described in the CMA Installation Instructions provided in the CMA  kit. Plug in all applicable cables to the rear of the system. Verify that all connections are secure. See Figure 1.  Figure 1: System with Cables Installed                      Page 2   ...
  • Page 5: Route The Power Cables Through The Strain Reliefs

    Cabling the Dell™ PowerEdge™ R710    2.2  Route the Power Cables Through the Strain Reliefs  After the tray and cables are installed, route the power cables through the strain reliefs located on the power  supply handles as shown in Figure 2.  Figure 2:  Routing Power Cables Through the Strain Reliefs                2.3  Routing the Cables Through the CMA  NOTE:  The CMA can be installed on either the right or left rear side of the rails.  Mounting the CMA on the side  opposite the power supplies (left side mount) is recommended; otherwise, the CMA must be disconnected in order  to remove the outer power supply. Refer to “Replacing a Power Supply on a PowerEdge R710 with CMA” later in  this white paper for details on power supply replacement.  NOTE:  For guidelines on how to route cables within the rack, refer to the Dell White Paper “Best Practices Guide  for Rack Enclosure”.  Left Side Mounting Instructions  1. Install the CMA on the left rear side of the rails by attaching both CMA housings to the attachment brackets on  the rails. See Figure 3.  2. Route the cables through the CMA while keeping any twisting of the cables to a minimum. If the cable bundle  includes a KVM dongle, place the dongle inside the CMA basket. Use the hook and loop straps on the CMA to  secure the cables.         Page 3   ...
  • Page 6 Cabling the Dell™ PowerEdge™ R710    Figure 3:  Routing the Cables Through the CMA              Cables entering CMA should have a small amount of slack   to avoid cable strain when CMA is extended.     NOTE: Do not store excess cable slack inside the CMA.
  • Page 7: Cabling A Poweredge R710 Without A Cma

    Cabling the Dell™ PowerEdge™ R710    Figure 4: Completed Left Side Mounted CMA Installation                      Right Side Mounting Instructions  Install the CMA on the right rear side of the rails by attaching both CMA housings to the attachment brackets on  the rails. Follow steps 2‐6 from the left side mounting instructions in the previous section.  See Figure 5 for an  example of a completed right side mounted CMA installation.  Figure 5: Completed Right Side Mounted CMA Installation                    Cabling a PowerEdge R710 without a CMA  NOTE:  The CMA on the Dell PowerEdge R710 is optional. Without the CMA installed, the system must be powered  down and all cables disconnected before it can be removed from the rack.  3.1  Routing the Cables  1. Plug in all applicable cables to the rear of the system, verifying that all connections are secure.    Page 5   ...
  • Page 8: Replacing A Power Supply On A Poweredge R710 With Cma

    Cabling the Dell™ PowerEdge™ R710    2. Using the hook and loop straps supplied with the rail kit, bundle the cables and secure them to either the left  rail or right rail CMA attachment brackets as described in the Rack Installation Guide. See Figure 6 for an  example of power cables secured to the right CMA bracket and data cables secured to the left CMA bracket. 3. It is recommended that the cables be secured to the outer brackets, but cables may be secured to the inner  brackets if desired.  Figure 6: Cable Routing Without a CMA                Replacing a Power Supply on a PowerEdge R710 with CMA  1. Remove the tray from under the CMA as described in the CMA Installation Instructions provided with the CMA  kit.  2. Swing the CMA into the service position. 3. Disconnect the power cord from the power supply and disengage the strain relief.  4. Remove and replace the power supply  If the CMA is attached to the right side and the outer power supply needs to be replaced, the inner  CMA attachment housing will need to be disconnected. While supporting the CMA with one hand,  remove and replace the power supply with the other hand as shown in Figure 7.    b. If the  CMA is attached to the right side and the inner power supply needs to be replaced, the CMA  does not need to be disconnected.  If the CMA is attached to the left side, both power supplies can be removed without disconnecting  the CMA.  5. Plug  in the power cord.  6. Re‐engage the strain relief.   7. Replace the CMA support tray.  ...
  • Page 9: Cabling A Poweredge R710 Installed In Static Rails

    Cabling the Dell™ PowerEdge™ R710    Figure 7: Replacing Outer Power Supply        Inner CMA attachment housing has been   disconnected                 Cabling a PowerEdge R710 Installed in Static Rails  NOTE:  The CMA is only compatible with sliding rails, and not with static rails.  1. Follow the instructions in the Rack Installation Guide included in the static rail kit to install the server into a 2‐ post or 4‐post rack.   2. Verify that the hook and loops straps provided with the static rail kit are installed to the rear of the rails.   3. Plug in all applicable cables to the rear of the system and verify that all connections are secure.  4. Using the hook and loop straps supplied with the rail kit, bundle the cables and secure them to either the left  rail or right rail as described in the Rack Installation Guide. See Figure 8. Figure 8: Cabling a System Installed in Static Rails           ...