Venting Installation - Desa S36 Owner's Operation And Installation Manual

Residental and outdoor woodburning fireplace
Table of Contents

Advertisement

Venting inStallatiOn

OPTIONAL OUTSIDE AIR KIT
(MODEL AK4/AK4F)
The installation of an outside air kit should be per-
formed during the rough framing of the fireplace
due to the nature of it's location. Outside combus-
tion air is accessed through a vented crawl space
(AK4F) or through a sidewall (AK4).
CAUTION: Combustion air
inlet ducts shall not terminate
in attic space.
Secure to Collars with Metal Tape,
Screws or Straps (Min. of 1/4" x 20"
in size)
Vented Crawl Space
(Check Local Codes
Before Installing in a
Vented Crawl Space)
Figure 5 - Outside Air Kit
CHIMNEY PIPE
The DESA chimney system consists of 12", 18",
24", 36" and 48" snap-lock, double-wall pipe
segments, planned for maximum adaptability
to individual site requirements. Actual lengths
gained after fitting overlaps must be taken into
consideration (lineal gain) and are given in the
lineal gain chart (see Figure 6). Lineal gain is the
actual measurable length of a part after two or more
parts are connected. For Canada, use chimney parts
designated "HT".
WARNING: The opening in the
collar around the chimney at the
top of the fireplace must not be
obstructed. Never use blown insula-
tion to fill the chimney enclosure.
6
Air Inlet
Location
Must Allow
For Bushes
or Snow
Air Inlet
Eyebrow
Vent Hood
Required for
Wall Installation
www.desatech.com
LINEAL GAIN
PART NO.
DESCRIPTION
36"
12-8DM
Pipe Section
12-8HT
18-8DM
Pipe Section
18-8HT
24-8DM
Pipe Section
24-8HT
36-8DM
Pipe Section
36-8HT
48-8DM
Pipe Section
48-8HT
RT-8DM
Round Termination
RTL-8DM Round Termination
Round Termination
RTT-8DM
with Slip Section
Round Termination
RTTL-8DM
with Slip Section
ET-8DM
Square Chase-Top
Square Chase-Top
ETO-8DM
with Mesh
Square Chase-Top
ETL-8DM
with Slip Section
Square Chase-Top
ETLO-8DM
with Mesh & Slip
* The lineal gain for the terminations is mea-
sured to the flue gas outlet height.
12" Galvanized
Outer Pipe
12
/
"
3
8
Stainless
Inner Pipe
Figure 6 - Lineal Gain
ASSEMBLY AND INSTALLATION OF
DOUBLE WALL CHIMNEY SYSTEM
Each double wall chimney section consists of a
galvanized outer pipe, a stainless steel inner flue
pipe and a wire spacer. The pipe sections must be as-
sembled independently as the chimney is installed.
When connecting chimney directly to the fireplace,
the inner flue pipe section must be installed first
with the lanced side up. The outer pipe section can
then be installed over the flue pipe section with the
hemmed end up. Press down on each pipe section
until the lances securely engage the hem on the fire-
place starter. The wire will assure the proper spacing
between the inner and outer pipe sections.
GAIN
Fireplace
10
16
23
34
46
6
7
6
23
8
21
7" to 1"*
12" to
2
Section
Hemmed
End
111026-01C
40"
/
"

8
/
"

8
/
"

8
/
"

8
/
"

8
" *
/
7
8
" *
/
3
4
/
" to
7
8
/
"*
1
8
/
" to
1
2
/
"*
1
2
12" *