Desa EFS33NR Owner's Operation And Installation Manual page 12

Desa owner's operation and installation manual unvented (vent-free) gas fireplace efs33nr,vsgf33nr,vsgf33nr,vsgf33pr
Table of Contents

Advertisement

INSTALLATION
12
Installing Gas Piping to Fireplace Location (Cont.)
Connecting Fireplace to Gas Supply
INSTALLATION
Continued
Installation must include an equipment shutoff valve, union, and
plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from fireplace (see Figure 18).
IMPORTANT: Install equipment shutoff valve in an accessible
location. The equipment shutoff valve is for turning on or shutting
off the gas to the appliance.
Check your building codes for any special requirements for locating
equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male NPT threads. This will prevent
excess sealant from going into pipe. Excess sealant in pipe could
result in clogged fireplace valves. Never use sealant on flare threads.
CAUTION: Use pipe joint sealant that is resistant
to liquid petroleum (LP) gas.
We recommend that you install a sediment trap in supply line as
shown in Figure 18. Locate sediment trap where it is within reach for
cleaning. Install in piping system between fuel supply and fireplace.
Locate sediment trap where trapped matter is not likely to freeze. A
sediment trap traps moisture and contaminants. This keeps them
from going into fireplace gas controls. If sediment trap is not
installed or is installed wrong, fireplace may not run properly.
CSA Design-Certified Equipment
Shutoff Valve With 1/8" NPT Tap*
3" Minimum
Cap
Pipe
Nipple Joint
Sediment Trap
Figure 18 - Gas Connection
* Purchase the optional CSA design-certified equipment shutoff
valve from your dealer. See Accessories, pages 28 through 30.
** Minimum inlet pressure for purpose of input adjustment.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Natural Gas
From Gas Meter
(5" W.C.** to 10.5" W.C.
Pressure)
Propane/LP
From External Regulator
(11" W.C.** to 14" W.C.
Pressure)
Tee
CONNECTING EQUIPMENT SHUTOFF VALVE
TO HEATER CONTROL
Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• Phillips screwdriver
• sealant (resistant to propane/LP gas, not provided)
1. Remove fireplace screen. Remove two screws that hold fire-
place screen in place for shipping. These screws are located
near top of screen. Discard screws. Lift fireplace screen up
and pull out to remove.
2. Remove screws that attach log base assembly to fireplace (see
Figure 19). Carefully lift up log base assembly and remove
from fireplace (see Figure 19).
Note: If adding the G8000A series brick liner accessory, install it
now. Follow instructions in G8000A accessory kit.
CAUTION: Do not pick up log base assembly by
burner. This could damage burner. Only handle base
by grates.
3. Route gas line (provided by installer) from equipment shutoff
valve to fireplace. Route flexible gas supply line through one
of the access holes.
NOTICE: Most building codes do not permit concealed
gas connections. A flexible gas line is provided to
allow accessibility from the fireplace (see Figure 20,
page 13). The flexible gas supply line connection to the
equipment shutoff valve should be accessible.
Figure 19 - Removing Log Base Assembly From Fireplace
107172

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Efs33praVsgf33prVsgf33praEfs33prVsgf33nr

Table of Contents