FIREPLACE
INSTALLATION
Continued
Installation must include an equipment shutoff
valve, union, and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up.
NPT tap must be upstream from fireplace (see
Figure 31).
IMPORTANT: Install main gas valve (equipment
shutoff valve) in an accessible location. The main
gas valve is for turning on or shutting off the gas
to the appliance.
Check your building codes for any special re-
quirements for locating equipment shutoff valve
to fireplaces.
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from
going into pipe. Excess sealant in pipe could result
in clogged fireplace valves.
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
We recommend that you install a sediment trap/
drip leg in supply line as shown in Figure 31. Lo-
cate sediment trap/drip leg where it is within reach
for cleaning. Install in piping system between fuel
supply and fireplace. Locate sediment trap/drip leg
where trapped matter is not likely to freeze. A sedi-
ment trap traps moisture and contaminants. This
keeps them from going into fireplace gas controls.
If sediment trap/drip leg is not installed or is in-
stalled wrong, fireplace may not run properly.
Approved Flexible
Gas Line
CSA Design-Certified
Equipment Shutoff
Valve with 1/8" NPT
Tap*
3" Minimum
Cap Pipe Nipple Tee Joint
Sediment Trap/Drip Leg
Figure 31 - Gas Connection
* The CSA design-certified equipment shutoff
valve may be supplied with the appliance or you
can purchase it from your retailer.
111986-01D
Natural - From Gas
Meter (5.5" W.C. to
10.5" W.C. Pressure)
Propane/LP
From External
Regulator (11"
W.C. to 14" W.C.
Pressure)
www.desatech.com
CONNECTING FIREpLACE TO GAS
SUppLY
Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• sealant (resistant to propane/LP gas, not
provided)
1. Open lower louver door panel by gently pull-
ing forward.
2. Route flexible gas line (provided by installer)
from equipment shutoff valve to fireplace.
Route flexible gas supply line through one of
the access holes on side of fireplace.
3. Attach flexible gas line from gas supply to
control valve (see Figure 32).
4. Check all gas connections for leaks. See
Checking Gas Connections.
To Gas Supply (Natural)
To External Regulator
(Propane/LP)
Flexible Gas
Line Do NOT
Kink
Figure 32 - Connecting Flexible Gas Line
to Control Valve
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
WARNING: Never use an
open flame to check for a leak.
Apply a noncorrosive leak detec-
tion fluid to all joints. Bubbles
forming show a leak. Correct all
leaks at once.
Equipment
Shutoff
Valve
Control
Valve
1