Firewerks SBJ18VNA Owner's Operation And Installation Manual page 9

Unvented (vent-free) gas log heater
Table of Contents

Advertisement

INSTALLATION
Continued
WARNING: Seal any fresh
air vents or ash clean-out doors
located on floor or wall of fire-
place. If not, drafting may cause
pilot outage or sooting. Use a
heat-resistant sealant. Do not
seal chimney flue damper.
WARNING: Never install
the heater
• in a bedroom or bathroom
unless installed as a vented
appliance, see page 12
• in a recreational vehicle
• where curtains, furniture,
clothing or other flammable ob-
jects are less than 42" from the
front, top or sides of heater
• in high traffic areas
• in windy or drafty areas
CAUTION: This heater cre-
ates warm air currents. These
currents move heat to wall sur-
faces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater
where impurities (such as, but
not limited to, tobacco smoke,
aromatic candles, cleaning flu-
ids, oil or kerosene lamps, etc.) in
the air exist, may discolor walls
or cause odors.
IMPORTANT: Vent-free heaters add moisture to
the air. Although this is beneficial, installing heater
in rooms without enough ventilation air may cause
mildew to form from too much moisture. See Air
for Combustion and Ventilation, page 6.
CHECK GAS TYPE
Use the correct gas type (natural or propane/LP) for
your unit. If your gas supply is not correct, do not
install in fireplace. Call dealer where you bought
the appliance for proper type of appliance.
114744-01C
is equipped for (natural or pro-
pane/LP) gas. Field conversion
is not permitted.
INSTALLATION AND CLEARANCES
FOR VENT-FREE OPERATION
minimum clearances. If you can,
provide greater clearances from
floor, ceiling and adjoining wall.
MINIMUM FIREPLACE CLEARANCE TO
SIDE WALL
LOG
SIZE
18"
24"
*Measured at 14" depth.
Allow adequate clearances for accessibility for
purposes of servicing and proper operation
Carefully follow the instructions below. This will
ensure safe installation into masonry, UL127-listed
manufactured fireplace or listed vent-free firebox.
Minimum Clearances For Side Combustible
Material, Side Wall and Ceiling
A. Clearances from the side of the fireplace
cabinet to any combustible material and wall
should follow diagram in Figure 4, page 10.
Example: The face of a mantel, bookshelf,
etc., is made of combustible material must be
4" from the side of the fireplace to the cabinet
(see Figure 4, page 10).
B. Clearances from the top of the fireplace open-
ing to the ceiling should not be less than 42".
www.desatech.com
WARNING: This appliance
WARNING: Maintain the
COMBUSTIBLE MATERIALS
CEILING
FLOOR
LOG SIZING REQUIREMENTS
MINIMUM FIREBOX SIZE
HEIGHT DEPTH FRONT
17"
14"
17"
14"
16"
42"
5"
REAR
WIDTH
WIDTH
24"
20"
28"
22"