Ventilation; Operation - Desa 30 Owner's Manual

Portable forced air heaters
Table of Contents

Advertisement

VENTILATION

OPERATION

099606
Follow the minimum fresh, outside air ventilation
requirements. If proper fresh, outside air ventilation is not
provided, carbon monoxide poisoning can occur. Provide
proper fresh, outside air ventilation before running heater.
Provide a fresh air opening of at least three square feet (2800 square cm) for each
100,000 BTU/Hr rating. Provide extra fresh air if more heaters are being used.
Example: A 150,000 BTU/Hr heater requires one of the following:
• a two-car garage door raised six inches (15.24 cm)
• a single-car garage door raised nine inches (22.86 cm)
• two, thirty-inch (76.20 cm) windows raised twelve inches (30.48 cm)
Review and understand the warnings in the Safety
Information Section. They are needed to safely operate this
heater. Follow all local codes when using this heater.
To Start Heater
1. Follow all ventilation and safety information.
2. Fill fuel tank with kerosene or No. 1 fuel oil.
3. Attach fuel cap.
4. Plug power cord of heater into standard 230 volt/50 hertz, grounded (earthed)
outlet. Use an extension cord if needed. Use only a three-wire, grounded
(earthed) extension cord.
Extension Cord Wire Size Requirements
Up to 100 feet (30.5 meters) long, use 16 AWG (1.0 mm
101 to 200 feet (30.6 to 61 meters) long, use 14 AWG (1.5 mm
Heater will start when power cord is plugged into outlet. If not, push in flame-
out control reset button (see Figures 6 thru 8).
Flame-
Out
Control
Reset
Button
Figure 6 - Flame-Out Control Reset
Button, 30/70,000 BTU/Hr
!
WARNING
!
WARNING
Flame-Out
Control
Reset
Button
Figure 7 - Flame-Out Control Reset
Button, 90,000 BTU/Hr
2
) conductor
2
) conductor
Continued
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents