Combustion Air And Ventilation Appliances; In Unconfined Spaces; In Confined Spaces - Kenmore 3314 - Power Miser 12 Owner's Manual

For potable water heating only, not suitable for space heating, not for use in mobile homes
Table of Contents

Advertisement

Donotapply insulation tothe topofthe water h eater, asthis
willinterfere withsafe operation ofthedrafthood.
Donotcover t heouter d oor, t hermostat ortemperature
&
pressure r elief v alve.
Donotallow insulation tocome within 2"(50.8 mm) o fthe
floor t oprevent blockage ofcombustion
airflow totheburner.
Donotcover t heinstruction manual. Keep itonthesideof
thewater h eater ornearby forfuture reference.
Doobtain newwarning a ndinstruction labels fromSears
forplacement ontheblanket directly over t heexisting labels.
Doinspect theinsulation blanket frequently tomake certain
it does notsag, t hereby o bstructing combustion airflow.
commence w ithin12inches (30cm)of thetop andone
commencing within 12inches (30cm)of thebottom ofthe
enclosures.
Combustion
Air and Ventilation
for
Appliances
Located
in Unconfined
Spaces
UNCONHNED
SPACE is space whose volume is not less than
50 cubic feet per 1,000 Btu per hour (4.8 m_ per kW) of the
aggregate input rating of all appliances installed in that space.
Rooms communicating
directly with the space in which the
appliances
are installed, through openings
not furnished with
doors, are considered
a part of the unconfined space.
In unconfined
spaces
in buildings,
infiltration
may be adequate
to provide
air for combustion,
ventilation
and dilution
of flue
gases.
However,
in buildings
of tight construction
(for example,
weather
stripping,
heavily insulated,
caulked,
vapor barrier, etc.),
additional
air may
need
to be provided
using
the methods
described
in Combustion
Air
and
Ventilation
for Appfiances
Located
in Confined
Spaces.
Combustion
Air and Ventilation
for
Appliances
Located
in Confined
Spaces
CONFINED
SPACE
is a space
whose
volume
is less
than
50 cubic
feet per 1,000
Btu per hour
(4.8 m 3 per kW)
of the
aggregate
input rating
of all appliances
installed
in that space.
A. ALL AIR FROM INSIDE BUILDINGS:
(See Figure
9 on page
9 and Figure
10 below)
The
confined
space
shall
be provided
with
two
permanent
openings
communicating
directly
with
an additional
room(s)
of sufficient
volume
so that the combined
volume
of all spaces
meets
the criteria
for an unconfined
space.
The total input
of
al! gas
utilization
equipment
installed
in the combined
space
shall
be considered
in making
this
determination.
Each
opening
shall
have
a minimum
free
area
of one square
inch
per 1,000
Btu per hour (22 cm2/kW)
of the total input rating
of al!
gas utilization
equipment
in the confined
space,
but not less
than
100
square
inches
(645
cm2).
One
opening
shall
FIGURE 10.
B. ALL A_R FROM
OUTDOORS:
(See Figures
9, 11,12 and 13)
The
confined
space
shall
be provided
with
two permanent
openings,
one commencing
within
12 inches
(30 cm) of the
top and one commencing
within
12 inches
(30 cm) from
the
bottom
of the enclosure.
The openings
shall
communicate
directly,
or by ducts, with the outdoors
or spaces
(crawl or attic)
that freely
communicate
with the outdoors.
ALT. HNL_=TAHR VENTHLATHON LOUVERS
FIGURE11.
When
directly communicating
with the outdoors,
each opening
shall have a minimum
free area of 1 square
inch per 4,000 Btu
per hour (5.5 cm_/kW) of total input rating of all equipment
in the
enclosure.
See
Figure
12.
When
communicating
with
the outdoors
through
vertical
ducts,
each
opening
shall
have
a minimum
free
area
of
1 square
inch per 4,000
BTU per hour (5.5 cm2/kW)
of total
input
rating
of al!
equipment
in the
enclosure.
See
Figure
12.
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Power miser 12153.331444153.331544

Table of Contents