Delta Electronics CANopen Slave Station Communication Module IFD9503 Instruction Manual

Delta electronics canopen slave station communication module instruction manual

Advertisement

Quick Links

Warning
This instruction only provides introductory information on electrical specifications, functions, wiring,
trouble-shooting and peripherals for IFD9503. Details of CANopen protocol are not included in this sheet. For more
information on CANopen protocol, please refer to relevant reference or literatures.
IFD9503 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity,
electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key
or specific tools are required to open the enclosure) in case danger and damage on the device may occur.
IFD9503 is used for controlling the operating machine and equipment. In order not to damage it, only qualified
professional staff familiar with the structure and operation of IFD9503 can install, operate, wire and repair it.
Please read this instruction sheet carefully before use and follow the sheet to operate IFD9503 in order to prevent
damages on the device or injuries to staff.
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all
the wiring again before switching on the power and DO NOT touch any terminal when the power is switched on.
Make sure the ground terminal
is correctly grounded in order to prevent electromagnetic interference.
Introduction
Thank you for choosing Delta IFD9503 CANopen slave station communication module. IFD9503 can be applied
to the connection between CANopen network and Delta's programmable logic controller, AC motor drive, servo
drive, temperature controller and human machine interface. In addition, the custom function of IFD9503 allows
the custom equipment with Modbus protocol to be connected to the CANopen network.
Functions & Services Supported
CAN2.0A protocol
CANopen DS301 V4.02
Process Data Object (PDO)
Network Management (NMT)
Service Data Object (SDO)
Product Profile & Outline
1
Communication port
2
Address setup rotary switch
3
Function setup DIP switch
4
Instructions on the DIP switch
5
SCAN indicator
6
RUN indicator
7
ERROR indicator
8
CANopen connector
DIN rail
DIN rail clip
Unit: mm
Specifications
CANopen Connector
Transmission method
CAN
Electrical isolation
500V DC
Type
Removable connector (5.08mm)
Transmission cable
2 communication cables, 2 power cables and 1 shielded cable
Communication
Message type
PDO, SDO, SYNC (synchronous object), Emergency (emergency object), NMT
Series transmission
10k, 20k, 50k, 125k, 250k, 500k, 800k, 1M bps (bits per second)
speed
Equipment type
0 (Non-Profile)
Company ID
477 (Delta Electronics, Inc.)
Electrical Specifications
Voltage
11 ~ 25V DC
Current
28mA (typical), 125mA impulse current (24 VDC)
Environment
Standards
IEC 61131-2, UL508
Storage: -25° C ~ 70° C (temperature), 5 ~ 95% (humidity)
Storage/operation
Operation: 0° C ~ 55° C (temperature), 50 ~ 95% (humidity); pollution degree 2
Shock/vibration
International Standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 &
immunity
IEC 68-2-27 (TEST Ea)
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1,000MHz, 10V/m
Interference immunity
EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
Certificates
CE, UL
Installation & Wiring
Install IFD9503 in an enclosure with sufficient space around it to
allow heat dissipation (see the figure).
DO NOT place the I/O signal wires and power supply wire in the
same wiring circuit.
Use 28-12AWG (1.5mm) single or multiple core wire on I/O wiring
28-12 AWG
terminals. See the figure for its specification.
The terminal screws shall be tightened to 4.75 kg-cm (4.12 in-lbs).
Use 60° C /75° C copper wires only.
<1 .5 mm
Components
CANopen Connector
To connector with CANopen, use the connector enclosed with IFD9503 or any connectors you can buy in the
store for wiring.
PIN
Signal
Description
1
V-
0V DC
2
CAN_L
Signal-
3
SHIELD
Shielded cable
4
CAN_H
Signal+
5
V+
24V DC
Address Switch
ENGLISH
The two rotary address setup switches set up the node addresses on the
CANopen network in hexadecimal form.
Setup range: 01 ~ 7F (00 and 80 ~ FF are forbidden)
Example:
If you need to set the node address of IFD9503 to 26 (H1A), simply switch the corresponding rotary switch ×16
0
to "1" and the corresponding rotary switch ×16
to "A".
Address Setting
Description
01 ~ 7F
Valid CANopen node address
00, 80 ~ FF
Invalid CANopen node address
Note: The changed value on the switch is only valid when IFD9503 is re-powered. When IFD9503 is operating,
changing the set value of the communication address will be invalid.
Function Switch
The DIP switch is to be used on the equipment connected to IFD9503, the
selection of communication ports and setting up the communication speed of
IFD9503 and the master station in CANopen.
Selecting the Equipment Connected to IFD9503
PIN1
PIN2
PIN3
Equipment
PIN1 PIN2 PIN3
ON
OFF
OFF
AC motor drive
ON
OFF
OFF
ON
OFF
PLC
OFF
ON
ON
ON
OFF
Temperature controller
ON
ON
OFF
OFF
ON
Servo drive
Example:
If the equipment connected to IFD9503 is a Delta servo drive, you only need to switch PIN3 of the DIP switch to
"ON", PIN1 and PIN2 to "OFF" and re-power IFD9503.
Note: The changed setting of the DIP switch is only valid when IFD9503 is re-powered. When IFD9503 is operating,
changing the setting of the DIP switch will be invalid.
Selecting IFD9503 Communication Mode
PIN4
PIN5
Communication Mode
PIN4 PIN5
OFF
OFF
RS-485
ON
OFF
ON
ON
RS-232
OFF
ON
Note: The changed setting of the communication mode is only valid when IFD9503 is re-powered. When IFD9503 is
operating, changing the setting of the communication mode will be invalid.
Setting up Baud Rate
PIN6
PIN7
PIN8
Baud Rate
PIN6 PIN7 PIN8
OFF
OFF
OFF
10kbps
OFF
OFF
ON
OFF
OFF
20kbps
ON
OFF
OFF
ON
OFF
50kbps
OFF
ON
ON
ON
OFF
125kbps
ON
ON
Note: The changed setting of the baud rate of CANopen is only valid when IFD9503 is re-powered. When IFD9503 is
operating, changing the baud rate will be invalid
Communication Ports on IFD9503
The communication ports on IFD9503 are used for the connection with other
equipments (Delta PLC, AC motor drive, temperature controller, servo drive,
HMI and custom equipments).
PORT 1
PORT 1 Sketch
Terminal No.
1
6
2
5
4
3
3
4
2
1
5
PORT1
6
Note: PORT 1 supports RS-485 communication mode only.
PORT 2
PORT 2 Sketch
Terminal No.
1
1
2
6
3
2
7
4
3
8
5
4
6
9
5
7
8
DB9 male
9
D
Note: PORT 2 supports RS-232 and RS-485 communication mode only.
D
D
IF D9503
LED Indicators & Troubleshooting
D
D> 50mm
RUN LED
LED Status
Indication
OFF
No power
Green light single
Stop
flash
Green light blinking
Pre-operation
Green light ON
Operating
Red light ON
NODE-ID error
ERROR LED
LED Status
Indication
OFF
No error
1 2 3 4 5
Red light double flash
Error control event occurs.
LED Status
Indication
H 16
1
H 16
0
Red light ON
BUS OFF
Scan LED
LED Status
Indication
1
OFF
No power
The correct information of the
Green light flash
equipment connected has not
been detected.
The communication with the
Green light ON
equipment connected is
normal.
Red light flash
CRC check fails
Connection fails, or no
Red light ON
connection
Equipment
ON
Human machine interface
ON
Custom equipment
ON
For internal system use
Communication Mode
Incorrect setting
Incorrect setting
Baud Rate
ON
250kbps
ON
500kbps
ON
800kbps
ON
1Mbps
注 意 事 項
PORT2
PORT1
CANopen
(OPEN TYPE)
Description
N.C.
GND
DATA-
DATA+
N.C.
N.C.
產 品 簡 介
IFD9503
RS-232
RS-485
N.C.
N.C.
CANopen
RXD
N.C.
支 援 的 功 能 與 服 務
TXD
DATA-
N.C.
N.C.
CAN2.0A
GND
N.C.
(PDO)
N.C.
N.C.
(SDO)
N.C.
N.C.
N.C.
DATA+
產 品 外 觀 及 各 部 介 紹
N.C.
N.C.
How to deal with it
Check the power of IFD9503 and make sure the
connection is normal.
---
---
尺 寸 單 位
---
Check if the setting of NODE-ID of IFD9503 is
功 能 規 格
correct.
CANopen
連 接 器
How to deal with it
IFD9503 operation is normal.
1. Check if the connection between IFD9503 and
the master station is intact.
2. Check if the communication between IFD9503
and the master station is normal.
How to deal with it
通 訊
1. Check if the BUS connection is normal.
2. Re-power IFD9503.
How to deal with it
ID
Check the power of IFD9503 and make sure the
電 氣 規 格
connection is normal.
Re-connect IFD9503 to the equipment.
環 境 規 格
1. Check if the communication cable between
IFD9503 and the equipment is correct.
2. Check if there is electromagnetic interference
nearby.
1. Check if the communication format of the
equipment is correct.
2. Check if IFD9503 and the equipment are correctly
connected.
3. Restart the connection and make sure the
communication cable meets the specification.
盤 內 安 裝 及 配 線
IFD9503
28-12AWG
<1.5mm
各 部 元 件 介 紹
CANopen
通 訊 連 接 器
CANopen
1
V-
2
CAN_L
3
SHIELD
4
CAN_H
5
V+
繁 體 中 文
IFD9503
CANopen
IFD9503
CANopen
CANopen
IFD9503
Modbus
CANopen DS301 V4.02
(NMT)
1
2
3
(DIP)
4
5
SCAN
6
RUN
7
ERROR
8
CANopen
DIN
: mm
DIN
CAN
500V DC
(5.08mm)
2
2
1
PDO SDO SYNC
Emergency
NMT
10k 20k 50k 125k 250k 500k 800k 1M bps
0 (Non-Profile)
477
11 ~ 25 VDC
28mA
125mA
(24V DC)
IEC 61131-2,UL508
-25° C ~ 70° C
5 ~ 95%
0° C ~ 55° C
50 ~ 95%
2
IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27
(TEST Ea)
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1000MHz, 10V/m
EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
CE
UL
IFD9503
/
28-12AWG 1.5mm
IFD9503
4.75 kg-cm 4.12 in-lbs
60° C/75° C
IFD9503
0V DC
Signal-
Signal+
1 2 3 4 5
24V DC

Advertisement

loading

Summary of Contents for Delta Electronics CANopen Slave Station Communication Module IFD9503

  • Page 1 (Delta PLC, AC motor drive, temperature controller, servo drive, 10k, 20k, 50k, 125k, 250k, 500k, 800k, 1M bps (bits per second) HMI and custom equipments). 0 (Non-Profile) PORT 1 477 (Delta Electronics, Inc.) PORT 1 Sketch 11 ~ 25V DC 28mA (typical), 125mA impulse current (24 VDC) PORT1 IEC 61131-2, UL508 Storage: -25°...