Compaq 231027-002 - ProLiant - DL320R01 Deployment Manual page 12

Telecommunication (telco) racks
Hide thumbs Also See for 231027-002 - ProLiant - DL320R01:
Table of Contents

Advertisement

Deploying ProLiant DL320 and DL360 Servers into Telecommunication (Telco) Racks
Figure 7: Intake
Figure 8: Intake
When installed in a 1U ultra-dense server deployment, air flow is sufficient to cool Compaq
ProLiant DL320 and ProLiant DL360 servers if the following criteria are met:
Ambient air temperature at the front of the unit does not exceed 95 F (35 C).
Relative humidity does not exceed 90 percent while operating.
Unrestricted airspace of at least 3 inches is provided in front of the server.
Unrestricted airspace of at least 3 inches is provided at the rear of the server.
Note: Cabling must not restrict airflow. The Compaq Telco Rack Option Kit includes a cable
management tray to provide appropriate clearance for airflow. Ensure airflow exiting the server's
exhaust vents is unrestricted if not using the cable management tray.