Installation Of Outdoor Unit; Connection Of Pipes - Haier HSU-09HVD03/R2 - annexe 2 Installation Manual

Room air conditioner
Hide thumbs Also See for HSU-09HVD03/R2 - annexe 2:
Table of Contents

Advertisement

1.Installation of Outdoor Unit

Drawing for the installation of indoor and outdoor units
Install according to

2.Connection of pipes

To bend a pipe, give the roundness as large as possible not to crush the pipe ,and the bending radius
should be 30 to 40 mm or longer.
Connecting the pipe of gas side first makes working easier.
The connection pipe is specialized for R410A.
The max vertical distance between the indoor unit and the outdoor unit is 5 m.
Half union
Spanner
Torque wrench
Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.
The standard pipe length is 5m. If it is over 5m, the function of the unit will be affected. If the pipe has
to be lengthened, the refrigerant should be charged, according to 20 g/m. But the charge of refrigerant
must be conducted by professional air conditioner engineer. Before adding additional refrigerant,
perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then charge
additional refrigerant.
3.Connection
Use the same method on indoor unit. Loosen the screws on terminal block and insert the plugs fully into
terminal block, then tighten the screws.
Insert the cable according to terminal number in the same manner as the indoor unit.
If wiring is not correct, proper operation can not be carried out and controller may be damaged.
Fix the cable with a clamp.
4.Attaching Drain-Elbow
If the drain-elbow is used, please attach it as
figure. (Note: Only for heat pump unit.)
5.Installation instruction on the outdoor part of the fresh air device
1.Remove the four screws of change-for-fresh-air box from the back cover.
2.Use six screws to fix the change new wind box onto the designated position on the outdoor unit.
3.Remove two screws of the pipe junction of the change new wind box, then insert the flared departure of
the change for fresh air tube into the pipe junction and then fix with the screws.
4.Use four screws to fix the change-for-fresh-air box onto the back cover, as illustrated:
Change-for-fresh-air box
Connecting terminal
Fresh air signal wire
(with guard ring)
Note:After wiring, the connecting terminals of outdoor unit and change-fresh-air as well as the wiring sheath should be
placed in the change-for-fresh-air box against the rain.
Outdoor unit
Flare nut
Forced fastening without careful centering
may damage the threads and cause a
leakage of gas.
Pipe Diameter (
Liquid side 6.35mm(1/4")
Gas side 9.52mm(3/8")
Gas side 12.7mm(1/2")
back
Screw
cover
hole
Fresh air box
Dust
Fresh air tube
filtration
mesh
6
Fastening torque
)
18N.m
40N.m
55N.m
Fresh air
Screw
box
Screw
Joint of tube
Fresh air tube
Fresh air tube
Flared departure