5.Purging Method:

Push the air out of the indoor unit
and piping as followes:
(1) Remove the valve cap on 2-way
valve in outdoor unit.
(2) Loosen by 1/2 turn the flare nut of
gas pipe, which is conneted to
3-way valve.
(3) Loosen 2-way valve by 90
hexagon wrench, and after approx.
10 sec tighten it up. Gas comes out
through flare nut on wide pipe. If no
gas is discharged, tighten flare nut
with specified torque.
(4) Open 2-way and 3-way valves
using specified torque.
(5) Tighten the caps on the valves
with specified torque.
Tighten torque N.m
Valve rod
Valve cap
20-25
When connecting pipe exceeds 5 meters, 20g or 60g(only for 22k) refrigerant
shall be added per exceeding meter . Charge according to the following list.
Piping length
Additional amount
No need
Piping length
Additional amount
No need
Note: When extending piping, air inside piping shall be removed by using external
refrigerant gas, charge according to the following list.
Brand new outdoor unit is charged 50g or 80g(only for 22k and 24k unit) more refrigerant than regulated weight.
Only for first installation, this extra 50g or 80g(only for 22k and 24k unit) can be used to purge air in pipes.
During this procedure, 50g or 80g(only for 22k and 24k unit) refrigerant will be discharged in piping.
(This must be strictly controlled within 90
Outdoor unit
o
using
7-9
for 9k 12k 18k
5m
7m
40g
for 22k 24k
5m
7m
120g
o
and 10 sec.)
2-way valve
6.35mm(1/4")
HSU-18C13
HSU-18CK03
10m
100g
10m
300g
7
3-way valve
12.7mm(1/2")
2-way valve
6.35mm(1/4")
9.52mm(3/8")
3-way valve
9.52mm(3/8")
12.7mm(1/2")
15.88mm(5/8")
HSU-09C12
HSU-12C12
HSU-09C13
HSU-12C13
HSU-22C13
HSU-24C13
HSU-09C03/Z1
HSU-12C03/Z1