CyberPower Office Tower Series UPS 1000 User Manual
CyberPower Office Tower Series UPS 1000 User Manual

CyberPower Office Tower Series UPS 1000 User Manual

Office tower series ups

Advertisement

Quick Links

eu.cyberpowersystems.com
Office Tower Series UPS
500 / 750 / 1000 / 1500VA
SAFETY WARNINGS
(SAVE THESE INSTRUCTIONS)
This manual contains important safety instructions. Please read and follow all instructions carefully
during installation and operation of the unit. Read this manual thoroughly before attempting to
unpack, install, or operate your UPS.
This equipment can be operated by any individuals with no previous training.
The socket-outlet shall be installed near the equipment and easily accessible.
During the installation of this equipment it should be assured that the sum of the leakage currents of
the UPS and the connected loads does not exceed 3.5mA.
Attention, hazardous through electric shock. Also with disconnection of this unit from the mains,
hazardous voltage still may be accessible through supply from battery. The battery supply should be
therefore disconnected in the plus and minus pole at the quick connectors of the battery when
maintenance or service work inside the UPS is necessary.
Do not dispose of batteries in a fire, the battery may explode.
Do not open or mutilate the battery or batteries, released electrolyte is harmful to the skin and eyes.
INSTALLING YOUR UPS SYSTEM
UNPACKING
Inspect the UPS upon receipt. The box should contain the following:
®
UPS Unit; PowerPanel
Plus Software Disk 1; Serial Interface Cable (DB-9) 1; Telephone
Cable 1; Power Cord-OP500E/ OP750E 2; Power Cord-OP1000UE/ OP1500UTE 4; USB
®
Cable 1; User Manual; PowerPanel
Plus Software User Manual.
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR
EQUIPMENT
1. Insure that the equipment plugged into the battery power-supplied outlets does not exceed the
UPS unit's rated capacity (500VA/300W for OP500E, 750VA/450W for OP750E, 1000VA/700W
for OP1000UE, 1500VA/900W for OP1500UTE). If rated unit capacities are exceeded, an
overload condition may occur and cause the UPS unit to shut down or the circuit breaker to trip.
2. If the power requirements of your equipment are listed in units other than Volt-Amps (VA), convert
Watts (W) or Amps (A) into VA by doing the calculations below. Note: The below equation only
calculates the maximum amount of VA that the equipment can use, not what is typically used by
the equipment at any one time. Users should expect usage requirements to be approximately
60% of below value.
TO ESTIMATE POWER REQUIREMENTS
1.
Watts (W) x 2.0 =
VA or
2. Add the totals up for all pieces of equipment and multiply this total by 0.6 to calculate actual
requirements. There are many factors that can affect the amount of power that your computer
system will require. The total load that you will be placing on the battery-powered outlets should not
exceed 80% of the unit's capacity.
HARDWARE INSTALLATION GUIDE
1. Connect the equipment to your UPS outlets. The IEC-IEC
power cords coming with the unit are used to connect your
computer and monitor to the UPS. Items such as copiers,
laser printers, vacuums, space heaters, or other large
electrical devices should not be connected to the UPS.
Please make sure that the total loads of your equipments are
less than the maximum total power load of your UPS.
2. Use your computer power cord to connect the UPS to a wall
outlet. Please avoid using extension cords and adapter plugs. (To maintain optimal battery charge,
leave the UPS plugged in at all times.)
3. Press the UPS power button to turn it on. The "Power On" indicator will be illuminated in "Green".
4. Install your software and accessories. To use the software, simply connect the enclosed serial
interface cable to the serial port on the UPS and an open serial port on the computer.
BASIC OPERATION
FRONT PANEL AND REAR PANEL DESCRIPTION
USING
POWER
ON
BATTERY
BOOST
BUCK
OP1000UE/1500UTE
User Manual
Amps (A) x 230 =
POWER
USING
ON
BATTERY
BOOST
BUCK
OP500E/750E
Power Switch
Power On Indicator
Using Battery Indicator
K01-0500E00-01
Buck Indicator
Battery Backup and Surge Protection Outlets
Surge Protection Outlets
Serial Port to PC
REMINDER: For contact closure communication function, please log onto our website at
eu.cyberpowersystems.com
USB Type B Port to PC
VA
Ethernet (RJ-45) Network Protection Ports
CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery.
Service the battery under the supervision of personnel knowledgeable of batteries and their
precautions. Keep unauthorized personnel away from batteries. If you have questions, contact
your dealer or call the number in this manual for information on battery replacement.
CAUTION! Use only the specified type of battery. See your dealer for replacement batteries.
CAUTION! The battery may present the risk of electrical shock. Do not dispose of batteries in a
fire, as it may explode. Follow all local ordinances regarding proper disposal of batteries.
CAUTION! Do not open or mutilate the batteries. Release electrolyte is harmful to the skin and eyes
and may be toxic.
CAUTION! A battery can present a high risk of short circuit current and electrical shock. Take the
following
precautions before replacing the battery:
1. Remove all watches, rings or other metal objects.
2. Only use tools with insulated handles.
3. DO NOT lay tools or other metal parts on top of battery or any battery terminals.
4. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of
ground. CONTACT WITH A GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK!
The likelihood of such shock will be reduced if such grounds are removed during installation
and maintenance (applicable to a UPS and a remote battery supply not having a grounded
circuit).
5.
Batteries are consider HAZARDOUS WASTE and must be disposed of properly. Contact your
local government for more information about proper disposal and recycling of batteries.
6. Turn off and unplug all connected equipment.
7
. T
urn the UPS off and unplug it from the AC power source.
.
8
Turn the UPS upside down.
Press the power button to turn the UPS ON or OFF.
This LED is illuminated when the utility condition is normal and the UPS outlets are
providing "clean power", free of surges and spikes.
This illuminates during utility failure, indicating that the battery is supplying power to
the battery-power supplied outlets.
Boost Indicator
This LED indicates that the UPS is operating in automatic voltage regulation mode.
When the led is illuminated continuously, it indicates that input under-voltage and that
the UPS unit boosts input voltage.
This LED indicates that the UPS is operating in automatic voltage regulation mode.
When the led is illuminated continuously, it indicates that input over-voltage and that
the UPS unit bucks the voltage.
The UPS provides battery powered and surge protected outlets for connected
equipment to insure temporary uninterrupted operation during a power failure and
against surges and spikes.
The UPS provides surge protected only outlet for connected
equipments against surges and spikes.
This port allows connection and communication from the DB-9 serial or USB port on
the computer to the UPS unit. The UPS communicates its status to the
®
PowerPanel
Plus software. This interface is also compatible with the UPS service
provided by Windows 98, Windows ME, Windows NT, Windows 2000, Windows
XP, Windows Server 2003.
to download the contact closure software patch.
This Port allows connection and communication from USB port on the computer to the
UPS unit. The UPS communicates its status to the PowerPanel
interface is also compatible with the UPS service provided by Windows 98, Windows
ME, Windows NT, Windows 2000, Windows XP, Windows Server 2003.
These ports are the protection for your computer network cable.
BATTERY REPLACEMENT AND STORAGE
®
Plus software. This

Advertisement

loading

Summary of Contents for CyberPower Office Tower Series UPS 1000

  • Page 1 eu.cyberpowersystems.com Office Tower Series UPS 500 / 750 / 1000 / 1500VA User Manual SAFETY WARNINGS (SAVE THESE INSTRUCTIONS) This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate your UPS.
  • Page 2 CyberPower Systems Inc. (USA) 4241 12th Avenue East Suite 400 Shakopee, MN 55379, U.S.A. Tel: +1 952 4039500, Fax: +1 952 4030009, E-MAIL: Entire contents copyright ©2004 CyberPower Systems B.V., All rights reserved. Reproduction in whole or in part without permission is prohibited. PowerPanel (USA) Inc.

This manual is also suitable for:

Office tower series ups 500Office tower series ups 750Professional rack mount ups 1500vaOp500eOp750eOp1000ue ... Show all