Omron S8M Product Manual page 5

S8m series digital multicircuit protector
Hide thumbs Also See for S8M:
Table of Contents

Advertisement

Construction and Nomenclature
Nomenclature
4 5 6 7
8
9
13
12
Note: The S8M-CP04-RS is shown above.
4 Tripping alarm output (TRP)
5 Alarm output (ALM)
6 Over-temperature output (TMP)
Internal circuit configuration
1
14
10
11
3
2
7 External tripping input (TRG)
No.
Name
1
Power Input Terminals
Connect to the input line.
(+V), ( V)
2
Branch Output
Connect to the load lines.
Terminals (+V), ( V)
Up to four branch outputs can be
connected.
3
Status Indicators
Indicate the connection and cutoff
(Red, Green)
status for each branch output.
Cut off: Red, Connected: Green (See
note 1.)
4
Tripping Alarm Output
Output (transistor: OFF) when the
(+, )
error tripping operation functions.
(See note 2.)
5
Alarm Output (+, )
Output (transistor: OFF) when a set
value for alarm detection is exceeded.
(See note 2.)
6
Over-temperature
Output (transistor: OFF) when a set
Output (+, )
value for over-temperature detection
is exceeded. (See note 2.)
7
External Tripping Input
The tripping operation can be
(+, )
executed with an externally input
signal.
8
Seven-segment Display
Displays measured values and set
(Red)
values.
9
Unit Indicators
V
Lit when the input voltage is being
(Orange)
displayed.
A
Lit when the output current is being
displayed.
Flashes when the peak output current
is being displayed.
kh
Lit when the run time is being
displayed.
C
Lit when the temperature is being
displayed.
s
Lit when setting the sequence time.
1 to 4 Lit or flashing when displaying branch
output information. (See note 3.)
10 Mode Key
Used to change the parameter being
displayed or to reset the peak hold
current value.
11 Up Key
Used to move to different setting
modes or to increase a set value.
12 Down Key
Used to move to different setting
modes or to decrease a set value.
13 Reset Key (RST)
Used when connecting branch
outputs for tripping operation. (See
note 4.)
14 Communications
Connect to the communications lines
Terminals (RD, SD, SG)
(RS-232C). (See note 5.)
Note: 1. For detailed display methods, refer to Status Indicators on
page 13.
2. Configured from independent circuits, and either sinking or
sourcing applications are possible.
3. Indicators 1 to 4 will not light except when the current is
being displayed.
4. Press for at least 3 s to enable operation.
5. Except for the S8M-CP04.
Digital Multicircuit Protector
Function
S8M
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S8m-cp04S8m-cp04-rS8m-cp04-rs

Table of Contents