■ Coil Voltages
Type-suffix for contactor types J7KN-10... to J7KN-74...
Suffix
Voltage Marking
to contactor
at the coil
type e.g.
J7KN-10-10-24 for 50Hz
for 60Hz
V
V
24
24
24
48
48
48
110
110
110-120 100
180
180-210 200-240 180
230
220-240 240
400
380-415 415-440 380
500
500-550 550-600 500
Standard voltages in bold type letter
Type-suffix for contactor types J7KN-85... to J7KN-110...
Suffix
Voltage Marking
to contactor
at the coil
type e.g.
J7KN-85-22-24 for 50Hz
for 60Hz
V
V
20
20
24
24
24
48
48
60
90
90
110-120 90
110
110-120
180
180-200 208-240 180
230
220-240 277
400
380-415 460-480 380
500
500-550 600-660 500
Standard voltages in bold type letter
36
Motor Contactor
Rated Control Voltage U
s
range for
50Hz
60Hz
min
max
min
max
V
V
V
V
22
24
24
27
44
48
48
52
110
110
122
210
200
240
220
240
240
264
415
415
460
550
550
600
Rated Control Voltage U
s
range for
50Hz
60Hz
min
max
min
max
V
V
V
V
20
22
24
26
24
27
29
32
47
52
56
62
100
108
120
110
122
132
146
200
208
240
220
240
264
288
415
455
498
550
600
660
J7KN
Type-suffix for contactor types J7KN-151... to J7KN-200...
Suffix
Voltage Marking
to contactor
at the coil
type e.g.
J7KN-151-230 for 50 Hz
for 60 Hz
V
V
24
24
24
48
48
48
110
110
120
230
220-240 220-240 220
400
380-415 380-415 380
Standard voltages in bold type letter
Rated Control Voltage U
s
range for
50Hz
60Hz
DC
min
max
min
max
max
V
V
V
V
V
24
24
24
24
24
48
48
48
48
48
110
120
110
120
110
240
220
240
220
415
380
415
-