HOW TO INSTALL

1. Installation method
■ Follow the illustration below to install. Do not install
facing directions other than what is shown in the
illustration.
Installation at the top of ceiling
Level
Outlet duct
Install the main
body horizontally
Provide a square
inspection hole of
at least 450 mm
2. Wiring method
■Open the condenser box cover.
Strip the wires according to the right illustration. The
earth wire of the power cord must be 10 ~ 15 mm longer
than other wire. Then bind the separated copper wires
into a bundle and insert bundle into the terminal deeply.
Make sure the screw column of terminal securely presses
on the copper wire and that the copper wire near insulation
layer is not exposed. (To avoid danger, it should be installed
by professionals and be sure to connect the earth wire.)
Up
The figure indicates the
surfaces in the left view
which can be installed
upwards.
Up
Mini sirocco fan
Inlet duct
Hanger bolt
Nut
Plain washer
FV-10/12/14/16CG2
Fan casing
Plain washer
FV-17/19/21CG2
Nut
(J)
Connect the circular duct to the
adapter using nonflammable tape
Up
Installation at the bottom of ceiling
Outlet duct
Level
Bolt, nuts, plain washers
Model
(No provide)
(B)
Inlet duct should have an upward
slope of at least 1/100
Slope
■ Do not install while the outlet
adapter faces up.
Inlet duct
Mini sirocco fan
Dimension L
M5
Bolt should reach 2-3 threads
through the nut
M10
Air flow
Slope
Level
Outlet duct should have a
downward slope of at least
1/100
Wiring each wire to sheaves
Power cord
60227 IEC 53 (RVV 0.75mm
Model No.
FV-10/12/14/16/17/19CG2
FV-21CG2
Outlet adapter
Earth wire
Cord clip
)
2
Dimension M
45 mm
40 mm
5