Preparation Before A Test Run Configuring Function Code Data - ADT iMaster-U1 Instruction Manual

Advanced simple inverter
Table of Contents

Advertisement

4.1.3 Preparation before a test run--Configuring function code data
Before running the motor, configure function code data specified in Table 4.1 in accordance with
the motor ratings and your system design values. The motor ratings are printed on the nameplate
of the motor. For your system design values, ask system designers about them.
• For details about how to change function code data, refer to Chapter 3, Section 3.4.1 "Setting
the function codes – "Data Setting." Refer to the function code H03 in Chapter 5 "FUNCTION
CODES" for the factory defaults of motor parameters. If any of them is different from the
default setting, change the function code data.
Table 4.1 Settings of Function Code Data before a Test Run
Function
code
F04
Base frequency
Rated voltage
F05
at base frequency
Motor parameter
P02
(Rated capacity)
Motor parameter
P03
(Rated current)
Motor selection
P99
Maximum
F03
frequency
Acceleration time1*
F07
Deceleration time1*
F08
Name
Function code data
Motor ratings
(printed on the
nameplate of
the motor)
System design values
*
the motor, increase
values so that they are
longer than your system
design values. If the
set time is short, the
inverter may not start
running the motor.
For a test-driving of
4-2
Factory setting
60.0 (Hz)
0 (V)
0 (V)
Applicable motor rated capacity
Rated current of applicable motor
0: Motor characteristics
60.0 (Hz)
6.00 (s)
6.00 (s)