Protective Functions - ADT iMaster-U1 Instruction Manual

Advanced simple inverter
Table of Contents

Advertisement

8.3 Protective Functions

Name
Overcurrent
- Stops the inverter output to protect the
protection
inverter from an overcurrent resulting from
overload.
Short-circuit
protection
- Stops the inverter output to protect the
inverter from an overcurrent due to a short
Ground fault
circuit in the output circuit.
protection
- Stops the inverter output to protect the
inverter from an overcurrent due to a ground
fault in the output circuit. This protection is
effective only when the inverter starts. If you
turn on the inverter without removing the
ground fault, this protection may not work.
Overvoltage
Stops the inverter output upon detection of
protection
overvoltage (400 VDC for 200 V series and 800
VDC for 400 V series) in the DC link bus.
This protection is not assured if excess AC line
voltage is applied inadvertently.
Under voltage
Stops the inverter output when the DC link bus voltage
protection
drops below the under voltage level (200 VDC for 200 V series
and 400VDC for 400 V series).
However, when F14 = 4 or 5, no alarm is output even if the DC link
bus voltage drops.
Input phase loss
Detects input
protection
This function prevents the inverter from undergoing heavy
stress that may be caused by input phase loss or inter-phase
voltage unbalance and may damage the inverter.
If connected load is light or a DC reactor is connected to the
inverter, this function may not detect input phase loss if any.
In single-phase series of inverters, this function is disabled by
factory default.
Output phase
Detects breaks in inverter output wiring at the start of running and
loss protection
during running, stopping the inverter output.
Inverter
- Stops the inverter output upon detecting excess heat sink
temperature in case of cooling fan failure or overload.
Braking
- Protects the braking resistor from overheat in accordance with
resistor
the setting of the electronic thermal overload relay for braking
resistor.
* It is necessary to set the function code data according to the
braking resistor used (built-in or external).
Overload
Stops the inverter output according to the inverter heat sink
protection
temperature and
calculated from the output current.
(Note) No alarm output depending upon the data setting of the function code.
Description
phase
loss,
stopping
the
switching element
During
acceleration
During
deceleration
During running
at constant
speed
During
acceleration
During
deceleration
During running
at constant
speed
(Stopped)
the
inverter
output.
temperature
8-5
"—": Not applicable.
LED
Alarm
monitor
output
displays
[30A,B,C]
Yes
OC1
OC2
OC3
Yes
OU1
OU2
OU3
Yes
LU
(Note)
Lin
Yes
Yes
OPL
Yes
OH1
Yes
dbH
Yes
OLU