Control Logic (Sink/Source) Change - Mitsubishi Electric FR-A802-F Series Instruction Manual

Table of Contents

Advertisement

2.6.3

Control logic (sink/source) change

Switch the control logic of input signals as necessary.
To change the control logic, change the jumper connector position on the control circuit board.
Connect the jumper connector to the connector pin of the desired control logic.
The control logic of input signals is initially set to the sink logic (SINK) for the type FM inverter.
The control logic of input signals is initially set to the source logic (SOURCE) for the type CA inverter.
(The output signals may be used in either the sink or source logic independently of the jumper connector position.)
NOTE
• Make sure that the jumper connector is installed correctly.
• Never change the control logic while power is ON.
54
2. INSTALLATION AND WIRING
2.6 Control circuit
Jumper connector
Jumper connector
Jumper connector
SOURCE
SINK
For sink logic