Fujitsu AUUH18LUAS Service Manual page 208

Cassette type
Table of Contents

Advertisement

¢ External heater output
External Input and
Function
Output PCB
setting
Rotary switch
60-11
Output signal
Off
On
Specifications of the signal output performance are as shown as follows:
Example: →hen set temperature (Ts) is set at 72°F (22°C);
• And room temperature (Tr) increase above 53.6°F (12°C), signal output is on.
• And Tr increase above 69.8°F (21°C), signal output is off.
• And Tr decrease below 66.2°F (19°C), signal output is on.
• And Tr decrease below 50°F (10°C), signal output is off.
The output also turns off in defrost operation.
3-5. Details of control output function
Output of indoor unit
External Input and
2, B, C
Output PCB
On
Heater turns on as shown in diagram of heating temperature
Heater turns off as shown in diagram of heating temperature
Other than Heating mode
Off
Error occurred
Forced thermo off
Fan stop protection
Tr-Ts=-1.8 °F (-1 °C)
Tr-Ts=-18 °F (-10 °C)
External output
CN47
Ex OUT 3
Condition
Tr-Ts
Off
Tr-Ts=-5.4 °F (-3 °C)
On
Tr-Ts=-22 °F (-12 °C)
Off
- (05-26) -
Output signal
Control
Off
On
Heater on
On
Off
Heater off
Off
On
Heater on
On
Off
Heater off
3. External input and output (for indoor unit)