General Data - Trane Thermafit AXM Installation, Operation And Maintenance Manual

Modular air-to-water heat pump
Table of Contents

Advertisement

General Data

Table 2. General data – Thermafit™ AXM air-to-water heat pump
Capacity (Tons)
General Unit
Number of Independent Refrigeration Circuits
R-454B Refrigerant Charge (lbs/module)
Load Fluid Volume(gal/module)
Compressor
Type
Quantity
Load Heat Exchanger
Type
Quantity
Fluid Volume (gal)
Fouling Factor (hr ft2-F/Btu)
Number of Circuits
Heating - Minimum/Maximum Leaving Water Temperatures (°F)
Heating - Minimum/Maximum Leaving Brine Temperatures (°F)
Cooling - Minimum/Maximum Leaving Water Temperatures (°F)
Cooling - Minimum/Maximum Leaving Brine Temperatures (°F)
Minimum Water/Brine Operating Pressure (psig)
Maximum Water/Brine Operating Pressure (psig)
Standard Option
Maximum Water/Brine Operating Pressure (psig)
Hi Pressure Option
Fans
Motor Type
HP
Fan Type
Airflow (cfm/module)
Coils
Fin Material
Fin/in (FPI)
Tube Material
Tube Diameter (mm)
Number of Rows
Coil Dimensions (qty)
ARTC-SVX009A-EN
30
DUAL
86
18.44
VAPOR INJECTED SCROLL
2
BRAZED PLATE
1
2.24
0.0001
2
90-140
90-140
42-65
42-65
0
200
300
EC
4.35
AXIAL
23,000
ALUMINUM
12
COPPER
0.375 (9.5)
4
40" x 88" (2)
9