Install Akd-8 (800-2000A) Retrofill Breaker - ABB AKR30S-800A Installation And Maintenance Manual

Retrofill circuit breakers
Table of Contents

Advertisement

Install AKD-8 (800-2000A) Retrofill Breaker
Danger
e
lt must be ensured that the supply power to the
compartment is turned off/ compartment is de-
'Shock and arc flash
Q
.
«
.
erplesion hacard
energized
for all the
incoming
and
outgoing
NFPA 70€ for safe work
meter
circuits of the LVS prior to any work being
conducted on it.
e
During the installation and related work on the
tasks.
e
Ensure only qualified personnel install, operate, service, and maintain all electrical
equipment.
After the existing breaker is removed, the compartment modified and secondary wiring
verified, the Retrofill breaker can now be installed in the AKD-8 switchgear, OEM switchgear
or switchboard.
Note : the preferred lifting method is always to use proper ABB lifting (spreader) bar. It will
provide the best chance of installing breakers, especially into the upper compartments,
without damaging the breakers. The WavePro small frame lifting bar had a 3rd lifting hook
at the front and it will not
fit on the retrofill breaker. Any time eye bolts (small frame
breakers) or large diameter holes (large Frame breakers) and generic lifting chains are used,
caution must be used to keep the chains to no less than 45 degree angle from horizontal to
avoid damaging the breaker side frames)
800A - 2000A Breakers : ABB Lifting Bar #2TSE431929R1000, old GE #0247B8961G002
3200A — 4000A Breakers : ABB Lifting Bar 2TSE431931R1000, old GE #0247B8961GO01
5000A Breakers : ABB Lifting Bar 2TSE431932R1000, old GE #0247B8961G003
1.
Verify that the breaker is in the disconnected and OPEN position before mounting it on
the rails. Refer to Figure 32
Indicator Position Location
(DISCONNECTED, TEST & CONNECTED)
30| © 2020 Emax 2 Retrofill Circuit Breakers 800-5000A
2TSA451009P0000 Rev-B