Addressing the detector
Set the device address using the rotary dials on the detector
head. The address range is 001-128.
Use the X10 dial to set the tens and the X1 dial to set the ones,
as shown in the figures below.
Device address 008

Device status

The device status is indicated by the status LED (Figure 1,
item 2), as shown in the table below.
State
Alarm
Prealarm
Isolation active [1]
Device fault
Located device [2]
Communicating [3]
[1] KE-DP3120W only.
[2] Indicates an active Locate Device command from the control panel.
[3] This indication can be disabled from the control panel or the
Configuration Utility application.

Detector sensitivity

Configure the detector sensitivity at the control panel or using
the Configuration Utility application.
Sensitivity settings
The available sensitivity settings are shown below.
Setting
Smoke sensitivity
1
High
2
Standard
3
Low
The default sensitivity setting depends on the control panel
Day/Night mode, as shown below.
Control panel mode
Day
Night
Smoke sensitivity settings are based on the following
obscuration values.
Smoke sensitivity
High
Standard
Low
2 / 23
Device address 112
Indication
Steady red LED
Flashing red LED
Steady yellow LED
Flashing yellow LED
Steady green LED
Flashing green LED
Default setting
2 (standard smoke sensitivity)
1 (high smoke sensitivity)
Obscuration
0.100 dB/m ±20%
0.150 dB/m ±20%
0.250 dB/m ±20%
ISO 7240 test fire support
The detectors support ISO 7240 test fires TF1, TF2, TF3, TF4,
TF5, TF8, and TF9. Test fires TF1, TF8, and TF9 are not
covered by EN 54-7.

Maintenance and testing

Maintenance and cleaning
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
Clean the outside of the detector using a damp cloth. If
required, clean the inside of the detector (to remove dust and
debris) using a vacuum cleaner.
Testing
Always test detectors after installation to ensure that the
detector communicates with the control panel. If the detector
does not communicate with the control panel, check that
duplicate addresses have not been assigned.

Specifications

Electrical
Operating voltage
Current consumption
Standby
KE-DP3120W
KE-DP3020W
Alarm
KE-DP3120W
KE-DP3020W
Polarity sensitive
Remote indicator alarm output
Remote indicator cable length
Isolation
Isolation specifications only apply to KE-DP3120W models with
an integrated short circuit isolator.
Current consumption (isolation
active)
Isolation voltage
Minimum
Maximum
Reconnect voltage
Minimum
Maximum
Rated current
Continuous (switch closed)
Switching (short circuit)
Leakage current
Series impedance
Maximum impedance [1]
Between the first isolator and
the control panel
Between each isolator
P/N 3102984-ML • REV 001 • ISS 29NOV23
17 to 29 VDC (4 to 11 V pulsed)
200 µA at 24 VDC
140 µA at 24 VDC
4.75 mA at 24 VDC
4.75 mA at 24 VDC
Yes
8 mA max.
30 m max.
5 mA
14 VDC
15.5 VDC
14 VDC
15.5 VDC
1.05 A
1.4 A
1 mA max.
0.08 Ω max.
13 Ω
13 Ω