Rinnai CX199i Installation And Operation Manual page 25

Tankless water heater
Hide thumbs Also See for CX199i:
Table of Contents

Advertisement

1. Install the water heater.
2. Determine the vent termination method—
horizontal or vertical, concentric, or twin
pipes, etc.
3. Determine proper location for wall or roof
penetration for each termination.
4. Install termination assembly as described
in this manual or in the vent
manufacturer's installation instructions.
5. Install intake air and exhaust vent piping
from water heater to termination.
6. Slope horizontal exhaust run towards the
water heater 1/4 in. per foot (21 mm per
meter). DO NOT slope intake air pipe
towards water heater.
7. Install vent supports and brackets allowing
for movement from expansion, as per vent
manufacturer's instructions or local code
requirements.
8. Install vent screen (supplied with water
heater) on PVC intake air and exhaust
termination elbows as illustrated below.
Press vent screen inside of
termination piece/elbow.
Secure vent screen to the elbow with
screw provided.
Figure 12: Vent Screen
Rinnai Tankless Water Heater Installation and Operation Manual
Check to determine whether local codes
supersede the following clearances:
Avoid termination locations near a dryer
vent.
Avoid termination locations near
commercial cooking exhaust.
Avoid termination locations near any air
inlets.
You must install a vent termination at
least 12 in. (30 cm) above the ground or
anticipated snow level.
The vent for this appliance shall not
terminate:
Over public walkways.
Near soffit vents or crawl space vents or
other areas where condensate or vapor
could create a nuisance or hazard or
cause property damage.
Where condensate or vapor could cause
damage or could be detrimental to the
operation of regulators, pressure relief
valves, or other equipment.
Listed below are important considerations for
locating vent termination under a soffit
(ventilated or unventilated or eave vent; or to
a deck or porch):
Do not install vent termination under a
soffit vent such that exhaust can enter the
soffit vent.
Install vent termination such that exhaust
and rising moisture will not collect under
eaves. Discoloration to the exterior of the
building could occur if installed too close.
Do not install the vent termination too
close under the soffit where it could
present recirculation of exhaust gases
back into the intake air part of the
termination.