Diagnostic Fault Code Storage And Retrieval - York GY8S160E30UH21 User's Information, Maintenance And Service Manual

High efficiency commercial belt drive
Table of Contents

Advertisement

106306-UUM-A-0205
7 RED FLASHES: This fault code indicates that the flame could not be
established. This no-light condition occurred 3 times (2 retries) during
the call for heat before locking out. Low gas pressure, faulty gas valve,
faulty hot surface igniter or burner problem may cause this. The furnace
will lock out for one hour and then restart.
8 RED FLASHES: This fault is indicated if the flame is lost 5 times (4
recycles) during the heating cycle. This could be caused by low gas
pressure or faulty gas valve. The furnace will lock out for one hour and
then restart.
9 RED FLASHES: Indicates reversed line voltage polarity or grounding
problem. Both heating and cooling operations will be affected. Check
polarity at furnace and branch. Check furnace grounding. Check that
flame probe is not shorted to chassis.
10 RED FLASHES: Gas valve energized with no call for heat. Check
gas valve and gas valve wiring.
11 RED FLASHES: This indicates that a primary or auxiliary limit switch
has opened its normally-closed contacts and has remained open for
more than five minutes. This condition is usually caused by a failed
blower motor or blower wheel.
STEADY ON RED: Control failure. Replace control board.
60-MINUTE AUTOMATIC RESET FROM LOCKOUT: This control
includes a "watchdog" type circuit that will reset from a lockout condition
after 60 minutes. Operational faults 6,7,8 will be reset. This provides
protection to an unoccupied structure if a temporary condition exists
causing a furnace malfunction. An example would be a low incoming
gas supply pressure preventing unit operation. When the gas pressure
is restored, at some point the "watchdog" would restart the unit and pro-
vide heat for the house.
NOTE: If a flame is detected the control flashes the LED for 1/8 of a
second and then enters a flame stabilization period.
(Seconds)
THERMOSTAT
OFF
INDUCER
OFF
IGNITOR
OFF
MAIN VALVE
OFF
HUMIDIFIER
OFF
ELECTRONIC
AIR CLEANER
OFF
CIRCULATING
BLOWER
OFF
FIGURE 11: Furnace Control Event Schedule
8
Thermostat Calling for Heat
0 2
17
ON
ON
ON
ON
IGNITION CONTROL (P/N 031-01973-000)
Normal flame sense current is approximately
Low flame signal warning starts at 1.5 microamps.
Low flame signal control lockout point is
DIAGNOSTIC FAULT CODE STORAGE AND
RETRIEVAL
The control in this furnace is equipped with memory that will store up to
five error codes to allow a service technician to diagnose problems
more easily. This memory will be retained even is power to the furnace
is lost. This feature should only be used by a qualified service tech-
nician.
The control stores up to five separate error codes. If more than five
error codes have occurred since the last reset, only the five most recent
will be retained. The furnace control board has a button, labeled "LAST
ERROR" that is used to retrieve error codes. This function will only work
if there are no active thermostat signals. So any call for heating, cooling
or continuous fan must be terminated before attempting to retrieve error
codes.
To retrieve the error codes, push the LAST ERROR button. The LED on
the control will then flash the error codes that are in memory, starting
with the most recent. There will be a two-second pause between each
flash code. After the error codes have all been displayed, the LED will
resume the normal slow green flash after a five second pause. To
repeat the series of error codes, push the button again.
If there are no error codes in memory, the LED will flash two green
flashes. To clear the memory, push the LAST ERROR button and hold it
for more than five seconds. The LED will flash three green flashes when
the memory has been cleared, then will resume the normal slow green
flash after a five-second pause.
22
52
Fan on Delay
30 Seconds
OFF
ON
OFF
ON
OFF
ON
OFF
3.7 microamps DC (µa)
0.9 microamps DC (µa)
Thermostat Satisfied
0
OFF
15 Sec.
Post
Purge
OFF
OFF
60, 90, 120, 180 SEC.
Selectable Fan Off Delay
Unitary Products Group
OFF
OFF
OFF
OFF