Location and orientation

Correct orientation and straight run requirements must be met for
accurate and repeatable flow measurements. Refer to
minimum pipe diameter distances from upstream disturbances.
Note
Consult the factory for instructions regarding use in square or
rectangular ducts.
"In plane A" means the sensor is in the same plane as the elbow.
"Out of plane A" means the bar is perpendicular to the plane of
the elbow.
If proper lengths of straight run are not available, position the
mounting such that 80% of the run is upstream and 20% is
downstream.
Use straightening vanes to reduce the required straight run
length.
Row 6 in
throttling valves that are partially opened, as well as control
valves.
Table 1-1: Straight Run Requirements
In plane
Out of plane
1
 
2
Quick Start Guide
Table 1-1
applies to gate, globe, plug, and other
Upstream pipe diameters
Without
straightening
vanes
In
plane A
8
N/A
11 
With
straightening
vanes
Out of
A'
C
plane A
10 
N/A  N/A
N/A
8
4
16
N/A
N/A
Quick Start Guide
Table 1-1
for
Downstream
pipe
diameters
C'
B
N/A
4
4
N/A
3