Figure 12
Figure 13
Power
supply
Connect the other end of the grounding lug wire to a grounding point at your site.
Step 7
If you have a Cisco 3620 router, apply the "Disconnect All Connections Before Opening the Cover"
Step 8
label to the upper part of the power supply. (See Figure 14.)
If you have a Cisco 3640 router, apply the "Disconnect All Connections Before Opening the Cover"
label to the upper part of the power supply, and apply the supplied voltage rating label for your power
supply to the lower part of the bracket. (See Figure 15.)
78-11640-01
Grounding Lug Fastened to Bracket on Cisco 3620 Power Supply with RPS
Ground lug
mounted on a
Cisco 3620 router
with Cisco RPS
Grounding Lug Fastened to Bracket on Cisco 3640 Power Supply
Ground lug
Installing the Grounding Lug on Cisco 2600 Series and Cisco 3600 Series Routers
Installing the Grounding Lug on a Cisco 3620 or Cisco 3640 Router
DC INPU T FOR USE WITH
CISC O RPS
+5V– – –14A , +12V – – –5A,
-12V– – –3A
Power
supply
Bracket