Malfunction
The system operates
▪ Check if air inlet or outlet of outdoor or
but cooling or heating
indoor unit is not blocked by obstacles.
is insufficient.
Remove any obstacles and make sure
the air can flow freely.
▪ Check if the air filter is not clogged (refer
to "Maintenance" in the indoor unit
manual).
▪ Check the temperature setting.
▪ Check the fan speed setting on your user
interface.
▪ Check for open doors or windows. Close
doors and windows to prevent wind from
coming in.
▪ Check if there are too many occupants in
the room during cooling operation. Check
if the heat source of the room is
excessive.
▪ Check if direct sunlight enters the room.
Use curtains or blinds.
▪ Check if the air flow angle is proper.
If after checking all above items, it is impossible to fix the problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).
8.1
Error codes: Overview
In case a malfunction code appears on the indoor unit user interface
display, contact your installer and inform the malfunction code, the
unit type, and serial number (you can find this information on the
nameplate of the unit).
For your reference, a list with malfunction codes is provided. You
can, depending on the level of the malfunction code, reset the code
by pushing the ON/OFF button. If not, ask your installer for advice.
Main code
External protection device was activated
The R32 sensor in one of the indoor units has
detected a refrigerant leak
The R32 sensor in one of the SV unit has detected a
refrigerant leak.
/
Safety system error (leak detection)
EEPROM failure (indoor)
Drain system malfunction (indoor/SV unit)
Fan motor malfunction (indoor)
Swing flap motor malfunction (indoor)
Expansion valve malfunction (indoor)
Drain malfunction (indoor unit)
Filter dust chamber malfunction (indoor)
Capacity setting malfunction (indoor)
Transmission malfunction between main PCB and sub
PCB (indoor)
Heat exchanger thermistor malfunction (indoor; liquid)
Heat exchanger thermistor malfunction (indoor; gas)
Suction air thermistor malfunction (indoor)
Discharge air thermistor malfunction (indoor)
Movement detector or floor temperature sensor
malfunction (indoor)
R32 sensor malfunction in one of the indoor units
R32 sensor end of lifetime in one of the indoor units
RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P739915-1 – 2023.12
Measure
Contents
(a)
(a)
(a)
(a)
Main code
R32 sensor end of lifetime<6 months in one of the
(a)
indoor units
Waiting for indoor unit R32 sensor replacement input
Waiting for SV unit replacement input
SV unit R32 sensor malfunction
Less than 6 months before the SV unit R32 sensor
end of lifetime
SV unit R32 sensor end of lifetime
User interface thermistor malfunction (indoor)
PCB malfunction (outdoor)
Current leakage detector was activated (outdoor)
High pressure switch was activated
Low pressure malfunction (outdoor)
Compressor lock detection (outdoor)
Fan motor malfunction (outdoor)
Electronic expansion valve malfunction (outdoor)
SV unit damper malfunction
Discharge temperature malfunction (outdoor)
Abnormal suction temperature (outdoor)
Refrigerant overcharge detection
High pressure switch malfunction
Low pressure switch malfunction
Fan motor malfunction (outdoor)
Ambient temperature sensor malfunction (outdoor)
Discharge temperature sensor malfunction (outdoor)
Suction temperature sensor malfunction (outdoor)
De-icing temperature sensor malfunction (outdoor) or
heat exchanger gas temperature sensor malfunction
(outdoor)
Liquid temperature sensor (after subcool HE)
malfunction (outdoor)
Liquid temperature sensor (coil) malfunction (outdoor)
Gas temperature sensor (after subcool HE)
malfunction (outdoor)
High pressure sensor malfunction (S1NPH)
Low pressure sensor malfunction (S1NPL)
INV PCB abnormal
Fin temperature abnormal
INV PCB abnormal
Compressor over current detected
Compressor lock (startup)
Transmission outdoor unit - inverter: INV transmission
trouble
INV unbalanced power supply voltage
Fin thermistor malfunction
Capacity setting malfunction (outdoor)
Abnormal low pressure drop, faulty expansion valve
Reversed power supply phase malfunction
INV voltage power shortage
System test run not yet executed
Faulty wiring indoor/SV unit/outdoor
Abnormal user interface - indoor communication
Faulty wiring to outdoor/outdoor
Warning because there is an error on another unit
(indoor/SV unit)