Toshiba RAV-GE6001A8P-T Installation Manual page 12

Table of Contents

Advertisement

Available languages

Available languages

Obstacle in front
Above unit is free
1. Single unit installation
2. Serial installation of two or more units
Obstacle also at the above unit
1,000 or
more
21-EN
1121901101.indd 12
Obstacles in both front and rear of unit
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of
the unit, should be lower than the height of the outdoor
unit.
Standard installation
1. Single unit installation
2. Serial installation of two or more units
300 or
300 or
more
more
Serial installation in front and rear
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of
the unit, should be lower than the height of the outdoor
unit.
Standard installation
1,000 or
300 or
1,500 or
2,000 or
200 or
more
more
more
more
more
– 11 –
Installation of outdoor unit
• Before installation, check the strength and
horizontalness of the base so that abnormal sounds
do not emanate.
• According to the following base diagram, fix the base
firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)
525
150
600
150
• As shown in the figure below, install the foundation
and vibration-proof rubber pads to directly support
the bottom surface of the fixing leg that is in contact
with and underneath the bottom plate of the outdoor
unit.
* When installing the foundation for an outdoor unit
with downward piping, consider the piping work.
Correct
Absorb vibration
with vibration-
proof rubber
pads
Fixing leg
Foundation
Correct
Bottom plate of
outdoor unit
Foundation
Support the bottom surface of the fixing
leg that is in contact with and underneath
the bottom plate of the outdoor unit.
Incorrect
Do not support
If only the end of
the outdoor unit
the fixing leg is
supported, it may
only with the
deform.
fixing leg.
Foundation
Set the out margin of the anchor bolt to 15 mm or less.
15 or less
When water is to be drained through the drain hose,
attach the following drain nipple and use the drain
hose (Inner dia.: 16 mm) sold on the market. Also
seal knockout hole and the screws securely with
silicone material, etc., to prevent water from leaking.
Some conditions may cause dewing or dripping of
water.
When collectively draining discharged water
completely, use a drain pan.
Drain nipple
Drain nipple
Knockout hole
22-EN
10/1/2562 11:10:12