Daikin VRV EMERION RXYQ-AATJA Design Manual page 20

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

RXYQ-AATJA / RXYQ-AAYDA
RXYQ144AATJA / RXYQ168AATJA / RXYQ192AATJA
Outdoor unit model No.
Power supply
★ 1
Nominal
Cooling
capacity
Rated
★ 2
Nominal
Heating
capacity
Rated
Casing color
Dimensions: (H × W × D)
Heat exchanger
Ty pe
Volume
Number of
Compressor
rev olutions
Motor output ×
Number of units
Starting method
Ty pe
Motor output
Fan
Airf low rate
Driv e
Liquid pipe
Connecting
pipes
Gas pipe
Weight
Sound pressure lev el
(ref erence data)
Sound power lev el
(ref erence data)
Saf ety dev ices
Def rost method
Capacity control
Ref rigerant name
Ref rigerant
Charge
Control
Standard accessories
Note:★1.Indoor temp.: 80°FDB (26.7°CDB) , 67°FWB (19.4°CWB) / Outdoor temp.: 95°FDB (35.0°CDB)
/ Rated capacity is certified under AHRI standard 1230.
★2.Indoor temp.: 70°FDB (21.1°CDB) / Outdoor temp.: 47°FDB (8.3°CDB) , 43°FWB (6.1°CWB)
/ Rated capacity is certified under AHRI standard 1230.
RXYQ144AATJA
3 phase, 60 Hz, 208/230 V
144,000 (42.2)
Btu/h
(kW)
138,000 (40.4)
162,000 (47.5)
Btu/h
(kW)
154,000 (45.1)
Iv ory white (5Y 7.5/1)
in.
65-3/8 × 48-13/16 × 30-1/8
(mm)
(1,660 × 1240 × 765)
Cross f in coil
Hermetically sealed scroll
ty pe
m³/h
11.6 + 17.6
r/min
5,496 + 5,196
kW
( 3.36 + 5.41 ) × 1
Sof t start
Propeller f an
kW
0.65 × 2
cf m
9,935 (281.3)
(m³/min)
Direct driv e
in.
ϕ1/2 (12.7) C1220T
(mm)
(brazing connection)
in.
ϕ1-1/8 (28.6) C1220T
(mm)
(brazing connection)
lbs (kg)
750 (340)
dB(A)
65
dB
85
High pressure switch,
Fan driv er ov erload protector,
Ov ercurrent f use,
Inv erter ov erload protector,
Leak detecting dev ice
Deicer
%
3 - 100
R410A
lbs (kg)
25.8 (11.7)
Electronic expansion v alv e
Installation manual,
Operation manual,
Connection pipes, Clamps
RXYQ168AATJA
3 phase, 60 Hz, 208/230 V
168,000 (49.2)
160,000 (46.9)
189,000 (55.4)
180,000 (52.8)
Iv ory white (5Y 7.5/1)
65-3/8 × 48-13/16 × 30-1/8
(1,660 × 1240 × 765)
Cross f in coil
Hermetically sealed scroll
ty pe
13.8 + 21
6,504 + 6,204
( 3.97 + 6.46 ) × 1
Sof t start
Propeller f an
0.65 × 2
9,935 (281.3)
Direct driv e
ϕ5/8 (15.9) C1220T
(brazing connection)
ϕ1-1/8 (28.6) C1220T
(brazing connection)
750 (340)
65
85
High pressure switch,
Fan driv er ov erload protector,
Ov ercurrent f use,
Inv erter ov erload protector,
Leak detecting dev ice
Deicer
2 - 100
R410A
25.8 (11.7)
Electronic expansion v alv e
Installation manual,
Operation manual,
Connection pipes, Clamps
18
EDUS342305-D
RXYQ192AATJA
3 phase, 60 Hz, 208/230 V
192,000 (56.3)
184,000 (53.9)
216,000 (63.3)
206,000 (60.4)
Iv ory white (5Y 7.5/1)
65-3/8 x 68-7/8 x 30-1/8
(1660 x 1750 x 765)
Cross f in coil
Hermetically sealed scroll
ty pe
19.1 + 20.1
5,628 + 5,934
( 5.86 + 6.18 ) × 1
Sof t start
Propeller f an
0.95 × 2
13,665 (386.9)
Direct driv e
ϕ5/8 (15.9) C1220T
(brazing connection)
ϕ1-1/8 (28.6) C1220T
(brazing connection)
904 (410)
67
88
High pressure switch,
Fan driv er ov erload protector,
Ov ercurrent f use,
Inv erter ov erload protector,
Leak detecting dev ice
Deicer
4 - 100
R410A
25.8 (11.7)
Electronic expansion v alv e
Installation manual,
Operation manual,
Connection pipes, Clamps
4D144722