Daikin RELQ72TBTJ Series Installation Manual page 16

System air conditioner
Hide thumbs Also See for RELQ72TBTJ Series:
Table of Contents

Advertisement

From branch to indoor
unit via 1 Branch
Selector unit
Allowable
length after
From branch to indoor
branch (*5)
unit via Branch Selec-
tor units connected in
pass through
(*4) In the case of an outdoor units multi system, "outdoor unit" should be read as the "first outdoor unit multi connection piping kit", seen from the
indoor units side.
(*5) A multi Branch Selector unit is to be considered as a branch (a single Branch Selector unit is not), so in the case where only 1 multi Branch Se-
lector unit is included in the system, the actual piping length from each branch port of the multi Branch Selector unit to each indoor units should
be ≤130 ft. (40 m).
(*6) In the case where the equivalent piping length from outdoor units to indoor units ≥295 ft. (90 m), make sure to upsize the liquid pipe of the main
pipe (see the figure below), referring to the table below. (Do not upsize the high/low pressure gas pipe and the suction gas pipe.)
Outdoor unit capacity type
RELQ 72,96 T type
RELQ 120,144 T type
RELQ 192,240 T type
(*7) It can be extended to ≤295 ft. (90 m) (if outdoor unit is lower than indoor unit, ≤195 ft. (60 m) by field setting [2-35] on page 34). See
[2-49]=Height difference setting on page 35.
(*8) For Branch Selector unit connected in pass through installation, all three conditions below must be satisfied.
1. Maximum capacity index of connectable indoor units for BSF6, 8Q54T* is ≤162 per Branch Selector unit.
2. Maximum capacity index of connectable indoor units under Branch Selector units connected in pass through is ≤230.
3. Total number of ports of Branch Selector units connected in pass through is ≤12.
(*9) When conditions listed in the table below are all satisfied, the allowable length restrictions after branch is ≤295 ft. (90 m). For Branch Selector
unit connected in pass through installation, also (*8) must be satisfied.
13
Actual piping length from the first REFNET joint or REFNET header to indoor
unit: ≤130 ft. (40 m) (*9)
(Example) 4 : e+h+j≤130 ft. (40 m), 7 : b+c+d+m+n+p≤130 ft. (40 m)
Actual piping length
Actual piping length from the first REFNET joint or REFNET header to indoor
unit: ≤130 ft. (40 m) (*8) (*9)
(Example) 11 : b+r+u+w≤130 ft. (40 m)
Liquid pipe
φ3/8 in. (9.5 mm) →
φ1/2 in. (12.7 mm)
φ1/2 in. (12.7 mm) →
φ5/8 in. (15.9 mm)
φ5/8 in. (15.9 mm) →
φ3/4 in. (19.1 mm)
First refrigerant
Outdoor units
branch kit
Branch
Selector
units
Main pipe
Upsize the liquid pipe
Indoor
units
English