381
Users Manual
Inrush Current Measurement (Jaw and Flexible Current Probe)
The Meter can capture the initial inrush current when starting a device such as a motor or light
ballast.
To measure the inrush current:
1. With the device under test off, turn the Meter Rotary Function Switch to
the Flexible Current Probe is being used for the measurement.
2. Center the Jaw or Flexible Current Probe around the device's live wire.
3. Push
on the Meter.
E
4. Turn on the device under test. The inrush current (spike) is displayed on the Meter display.
See
Figure
5.
CAT
1000 V
CAT
600 V
Frequency Measurement (Jaw and Flexible Current Probe)
To measure frequency:
1. Turn the Meter Rotary Function Switch to
used for the measurement.
2. Center the Jaw or Flexible Current Probe around the measurement source.
3. Push
on the Meter to shift to Hz. The frequency is displayed on the Meter display.
Z
12
Figure 5. Inrush Current Measurement