3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature
and outdoor heat exchanger temperature as follows.
1st defrost
Compressor
integrating
operation:
Over 22 minutes
Outdoor
Outdoor
heat exchanger
heat exchanger
temperature:
temperature:
Below - 5°C
Below - 9°C
Heating operation start : Compressor ON
2nd and later defrost
Compressor
Compressor
integrating
integrating
operation:
operation:
Over 62 minutes
Over 35 minutes
Outdoor
heat exchanger
temperature:
Below - 6°C
Defrost Indicator:
[Operation lamp]
7 sec ON / 2 sec OFF
Outdoor heat exchanger temperature: Over 13°C
Compressor ON time: Maximum 15 minutes
(Not defrosted for 10 minutes)
Defrost start
Outdoor fan : OFF
Compressor speed : 0 rps
EEV : 480pulse
4-way valve : OFF
Compressor speed : 55rps
or
Defrost end
01-20
Integrating defrost
(Constant monitoring)
Compressor
Compressor
OFF count :
integrating
40 times
operation:
Over 240 minutes
Outdoor
heat exchanger
temperature:
Below - 3°C