Ariston CLAS X Training Manual page 14

Wall hang boiler, conventional compact
Table of Contents

Advertisement

Training manual CLAS X
After flame detection the boiler is free to
modulate the power according to the required
thermal load. Modulation is carried out
between the maximum heating power values
(adjustable from the control panel with
parameter 231) and the minimum power
value (set made on the gas valve). The shut
down temperature of the burner is operated
 1° min after flame detection:
T off = T set-point + 8°C
 2° min after flame detection:
T off = T set-point + 6°C
 starting from the 3
detection:
T off = T set-point + 4°C
This logic is used to prevent the burner from
shutting down too quickly with the system at
temperature.
Next ignition can be delayed from 0 to 7
minutes (default value = 2 min., adjustable
from the control panel with parameter 236)
The pump has 2 speeds that are operated by
the control of the heating delivery-return ΔT. It
is operated as follows:
 ΔT del-ret < ΔT – 2°C → V2 pump speed
 Δt del- ret > ΔT → V3 pump speed
where: ΔT= 20°C (default value can be
sent by parameter
30°C).
Speed switching is carried out with a 5 minute
delay (non-settable value) raising or
diminishing
.
Performed from the flow and return NTC. If
the temperature rise 102°C a lock out occurs,
indicated on the display with
N.B. Starting from heating request, the "limit temperature" (88°C, not adjustable fixed
value) remains on executed by the primary exchanger outlet probe (NTC 1).
If there is a bad circulation through the heating system, the automatic by-pass can be
opened (max capacity 350 l/h).
as follows:
rd
min after flame
239
between 10 and
1
01.
FLAME
MODULATION
PUMP
Speed control
Overheat control
Pag. 14 di 69