Fujitsu AIRSTAGE ABUA12TLAV2 Installation Manual page 13

Indoor unit (floor / ceiling type)
Table of Contents

Advertisement

Function details
Function
Function
Setting number
number
00 Standard
Filter indicator
11
01 Longer
interval
02 Shorter
00 Enable
01 Disable
Filter indicator
13
action
Display only on
02
central remote
controller
(Forbidden)
20
00
(Forbidden)
23
00
00 Standard
Horizontal
swing airfl ow
24
01 Left half
direction
02 Right half
(Forbidden)
26
31
00 Standard
Cool air
temperature
30
01 Adjust (1)
trigger
02 Adjust (2)
00 Standard
Heat air
01 Adjust (1)
temperature
31
02 Adjust (2)
trigger
03 Adjust (3)
00 Enable
Auto restart
40
(*1)
01 Disable
00 Super low
Cool Air
43
Follow the
Prevention
setting on
01
the remote
controller
00 Start/Stop
External
Emergency
46
01
control
stop
02 Forced stop
00 All
Error report
Display only on
47
target
01
central remote
controller
Follow the
Fan setting
00
setting on the
when cooling
remote controller
49
thermostat
OFF
01 Stop
00 Mode 0
01 Mode 1
Switching
functions
02 Mode 2
for external
03 Mode 3
inputs and
60
04 Mode 4
external
05 Mode 5
outputs
terminals
06 Mode 6
(*2)
07 Mode 7
08 Mode 8
Default
Details
Adjust the fi lter cleaning interval
notifi cation. If the notifi cation is too
early, change to setting 01. If the
notifi cation is too late, change to
setting 02.
Enable or disable the fi lter indicator.
Setting 02 is for use with a central
remote controller.
Adjust the horizontal swing airfl ow
direction.
(For horizontal swing equipped
models)
Adjust the cool air trigger temperature.
To lower the trigger temperature,
use setting 01. To raise the trigger
temperature, use setting 02.
Adjust the heat air trigger temperature.
To lower the trigger temperature by 11
degrees F (6 degrees C), use setting
01. To lower the trigger temperature by
7 degrees F (4 degrees C), use setting
02. To raise the trigger temperature,
use setting 03.
Enable or disable automatic system
restart after a power outage.
Restrain the cold airfl ow with making
the airfl ow lower when starting heating
operation. To correspond to the
ventilation, set to 01.
Allow an external controller to start
or stop the system, or to perform an
emergency stop.
* If an emergency stop is performed
from an external controller, all
refrigerant systems will be disabled.
* If forced stop is set, indoor unit stops
by the input to the external input
terminals, and Start/Stop by a remote
controller is restricted.
Change the target for reporting
errors. Errors can either be reported
in all locations, or only on the central
remote controller.
When set to 01, the fan stops when
the thermostat is OFF in cooling
operation. Connection of the wired
remote controller (2-wire type) and
switching its thermistor are necessary.
• Set this function when connecting
the VRF system to a ventilator,
economizer, humidifi er, or other
external device.
• The connection terminal functions
can be changed depending on
the type of external device. For
details of the connection terminal
functions, see the Design & Tech-
nical Manual.
Function
Function
Setting number
number
Auxiliary
00
heater con-
trol 1
Auxiliary
01
heater con-
trol 2
Heat pump
02
prohibition
control
Heater selec-
tion control
03
using outdoor
temperature 1
Heater selec-
tion control
04
using outdoor
Control
temperature 2
switching
61
Auxiliary
of external
heater control
heaters
05
by outdoor
temperature 3
Auxiliary heat
06
pump control
Auxiliary heat
pump control
07
by outdoor
temperature 1
Auxiliary heat
pump control
08
by outdoor
temperature 2
Auxiliary heat
pump control
09
by outdoor
temperature 3
00 Setting 0
01 Setting 1
02 Setting 2
03 Setting 3
04 Setting 4
05 Setting 5
06 Setting 6
07 Setting 7
Operating
temperature
08 Setting 8
switching
62
09 Setting 9
of external
heaters
10 Setting 10
11 Setting 11
12 Setting 12
13 Setting 13
14 Setting 14
15 Setting 15
16 Setting 16
17 Setting 17
Single setpoint
auto mode
00
(traditional)
Auto mode
68
type (*3)
Dual setpoint
01
auto mode
00 0°F (0°C)
01 1°F (0.5°C)
02 2°F (1.0°C)
03 3°F (1.5°C)
04 4°F (2.0°C)
Deadband
69
value (*3)
05 5°F (2.5°C)
06 6°F (3.0°C)
07 7°F (3.5°C)
08 8°F (4.0°C)
09 9°F (4.5°C)
(Forbidden)
70
00
00 Disable
01 1 minutes
Standby
time for
02 2 minutes
auxiliary
71
equipment
operation
98 98 minutes
99 99 minutes
Default
Details
Sets the control method for the
external heater being used. For
details of the control method, see
the Design & Technical Manual.
• Sets the temperature conditions
when the external heater is ON.
• For the temperature conditions,
see "Temperature conditions
when the external heater is ON".
For a more detailed explana-
tion, see the Design & Technical
Manual.
Switch the setting method of
auto mode to single or dual
(cooling/heating).
For heat pump systems, it is
necessary to set the master
indoor unit (by wired remote
controller).
Choose the minimum temperature
between cooling and heating
settings (deadband) for Dual
setpoint auto mode (set in No. 68).
Sets the standby time until the
auxiliary equipment operation
starts during primary equipment
operation.
En-12