Wiring And Start Up - Aprilaire 5000 Installation Instructions Manual

Electronic air cleaner
Hide thumbs Also See for 5000:
Table of Contents

Advertisement

WARNING
ELECTRIC SHOCK HAZARD: 120 volts may cause serious
injury from electric shock. Disconnect electrical power to
the HVAC system before starting installation or servicing.
Leave power disconnected until installation/service is
completed.
1. Install a grounded (earth ground) 120-volt single receptacle
outlet in accordance with NEC Standards and local codes,
into which the EAC will be plugged . This outlet is to be live
only when the furnace/air handler blower is running .
FOR EQUIPMENT WITH EAC TERMINALS:
a. Install a single-receptacle outlet to the furnace/air
handler wired as shown in FIGURE 10 .
b. Use a marker or label to identify the outlet as EAC USE
ONLY .
FOR 120-VOLT EQUIPMENT WITHOUT EAC TERMINALS:
a. Use an Aprilaire Model 51 Current Sensing Relay to wire
a single receptacle outlet as shown in FIGURE 11 . Refer to
the instructions provided with the Model 51 for details on
wiring requirements .
b. For blowers that are 1/2 hp or larger, clamp the Model 51
around the common wire of the blower . See FIGURE 12 .
c. For blowers that are less than 1/2 hp, clamp the Model
51 around two wraps of the common wire as shown in
FIGURE 12 .
d. Use a marker or label to identify the outlet as EAC USE
ONLY .
FOR 240-VOLT EQUIPMENT WITHOUT EAC TERMINALS:
a. Install a 2:1 step down transformer to get 120-volt service .
Use the instructions provided with the transformer to
ensure it is properly installed . Do not use ground as the
common connection for the outlet .
b. Follow the instructions FOR 120-VOLT EQUIPMENT
WITHOUT EAC TERMINALS above, except double the
number of wraps around which the Model 51 is clamped .
2. Press the power cord into the slot in the side of the power
pack (door) so that the plug is directed toward the installed
outlet .
3. Install the door on the housing (with the inner assembly
installed in the housing) . Place the bottom of the door on
the lower door retainer, then swing the door toward the
upper door retainer and snap into place .
4. With the door ON/OFF switch in the OFF position, plug the
door into the installed outlet .

WIRING AND START UP

DO NOT PLUG THE AIR CLEANER INTO AN OUTLET THAT IS
ALWAYS LIVE. The outlet must only be live when the HVAC
system fan is operating. Failure to properly wire the outlet
can result in excessive ozone production.
5. Restore power to the furnace/air handler .
6. Turn on the heating or continuous fan (whichever uses the
slowest fan speed) and verify that the blue light on the door
is not on (see FIGURE 13) .
7. Turn ON the door switch .
8. Verify that the blue light on the door turns on (see
FIGURE 13) .
9. If the light is on, turn off the heating or fan and verify
that the light on the door turns off . If the light turns off,
installation is complete . If the light on the door does not turn
on and off as described, continue with Step 10 .
10. If the light stays on after the blower has stopped running,
the outlet is continuously live and must be rewired in
accordance with Step 1 .
11. If the light flashes on, then turns off, or if the light does not
come on at all, refer to the TROUBLESHOOTING GUIDE on
page 9 .
CAUTION
7

Advertisement

Table of Contents
loading

Table of Contents