OPERATING PROCEDURE
13. Removing the compressor (MC)
(1) Remove the service panel. (See Photo 1)
(2) Recover refrigerant.
(3) Remove the electrical parts box. (See Photo 3-1)
(4) Remove the valve bed. (See Photo 3-1)
(5) Remove the cover panel (front). (See Photo 3-1)
(6) Remove the cover panel (rear). (See Photo 3-1)
(7) Remove the side panel (top). (See Photo 3-2)
(8) Remove the comp felt (body). (See Photo 3-2)
(9) Remove the side panel (R). (See Photo 1)
(10) Remove the thermistor <Discharge> (TH4), thermistor
<Suction> (TH32), thermistor <Comp. Surface> (TH33)
and thermal protector.
(11) Remove the 4-way valve coil and LEV coil.
(12) Disconnect the lead wire from the pressure switch.
(13) Remove the hic top support fixing screw (1 for front/ 4 ×
10) to remove the hic top support.*
(14) Remove the welded part (Joint part of the compressor)
of piping (SWM model for 2 positions, SHWM model for 3
positions), then slide the piping upward to remove it.
(15) Remove the compressor fixing nuts (3 for top/ M6) to
remove the compressor.
Note 1: Recover refrigerant without spreading it in the air.
2: Tighten the nuts of compressor with a torque of
4 ± 0.4 N·m.
*
For SHWM model only
1
14. Removing the reactor (ACL1, ACL2, ACL3)
(Y-type model only)
(1) Remove the electrical parts box. (See Photo 3-1)
(2) Remove the reactor assy fixing screws (4 for right/ 5 ×
12), then slide the reactor assy upward to remove it.
(3) Remove the reactor fixing screws (4 for front/ 4 × 10) to
remove each reactor on the reactor assy.
Note 1: Pay extra attention when handling the reactor and
its assembly since it is very heavy (4 kg for each
reactor).
OCH809A
Photo 13
1
Photo 14
79
PHOTOS/ FIGURES
Compressor
Reactor assy
Reactors
Hic top support *