Mitsubishi Electric PUZ-SWM60VAA Service Manual page 58

Air to water heat pump units
Table of Contents

Advertisement

SW2 setting
The outdoor unit setting information
ON
1
2 3 4 5 6
The indoor pipe temperature/Liquid
ON
(TH2(1))
Indoor 1
1
2 3 4 5 6
−39 to 88
The indoor pipe temperature/Cond./Eva.
(TH5(1))
Indoor1
ON
Outdoor condensing temperature (T63HS)
Condenser: T63HS
1
2 3 4 5 6
Evaporator: TH5
-39 to 88
The indoor pipe temperature/Liquid
ON
(TH2(2))
Indoor 2
−39 to 88
1
2 3 4 5 6
The indoor pipe temperature/Cond./Eva.
ON
(TH5(2))
Indoor 2
1
2 3 4 5 6
−39 to 88
The return water temperature (THW2)
ON
0 to 60
1
2 3 4 5 6
The target flow water temperature
ON
0 to 80
1
2 3 4 5 6
The outdoor pipe temperature/Cond./
Eva.(TH6 or T63HS)
ON
Condenser: T63HS
Evaporator: TH6
1
2 3 4 5 6
-39 to 88
The ambient temperature (TH7)
ON
−39 to 88
1
2 3 4 5 6
The outdoor heat sink temperature
(TH8)
ON
−40 to 200
1
2 3 4 5 6
ON
The discharge superheat (SHd)
0 to 255
SHd = TH4 or TH33*−T63HS
1
2 3 4 5 6
* Chose higher one
OCH809A
Display detail
The black square (
Explanation for display
• The tens digit (Total display for applied setting)
Setting details
H·P / Cooling only 0: H·P
Single phase / 3 phase 0: Single phase 2: 3 phase
• The ones digit
Setting details
Defrosting switch
0: Normal
(Example) When heat pump, 3 phase and defrost-
ing (normal) are set up, "20" is displayed.
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
0 to 60
0 to 80
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
−40 to 200
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(When the temperature is 100°C or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
0 to 255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
58
) indicates a switch position.
Display details
1: Cooling only
Code
display
Display details
1: For high humidity
Unit
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C