RS485 CONNECTION SETTINGS
Communication frame structure
Name
Number of bytes
Default interval
Start: Set a default range of 3.65 ms or more between signals (without communication time).
1
Machine address: Specify a machine address to connect the RS485 module. (Refer to "List of the machine
2
addresses" for the setting method.)
Function code:
3
Data: The composition of the data section varies with the function code and register address.
4
(Refer to "Cases of Setting Communication Framework".)
Check code: The calculated value of a 16-bit CRC in the Modbus-RTU mode.
5
·For CRC calculation, refer to below:
1. Preset a 16-bit register as 0FFFFH (all 1s), which is called a CRC register.
2. Perform an exclusive-or (XOR) operation between the 8 bits of the first byte in the data
frame and the low byte in the CRC register, and store the result back to the CRC register.
3. Shift the CRC register one bit to the right, put a 0 in the most significant bit, shift out the
least significant bit, and perform a detection.
4. If the least significant bit is 0: repeat Step 3 (for the next bit shift); if the least significant
bit is1: perform an exclusive-or (XOR) operation between the CRC register and the preset
fixed value (0A001H).
5. Repeat Steps 3 and 4 until 8 bit shifts are performed. This completes the bit manipulation
of an 8-bit byte.
6. Repeat Steps 2 through 5 to manipulate the next 8 bits until all byte manipulations are
complete.
7. The final value of the CRC register is the CRC value.
End: Set a default range of over 3.65 ms between signals (without communication time).
6

LIST OF REGISTER ADDRESSES

Below is a list of register addresses used by the RS485 module for communication.
Register
Data name
address
Running state
0x0001
Running mode
0x0002
8
1
Start
Machine address
Function code
0x03
0x06
Writing complex register
0x10
Function
Read/
code
Write
0x03
0x06
R/W
0x10
0x03
0x06
R/W
0x10
2
3
Function code
1
1
Content
Reading register
Writing register
Data length
[Byte]
2
2
4
Data
Check code
n
Function description
Reads register values.
Writes a (single) set value.
Writes a (complex) set value.
Type
0x00: OFF
UINT16
0x01: ON
0xFF: set Skip (keep the current setting)
0x00: Heat exchange
UINT16
0x01: Normal ventilation
0xFF: set Skip (keep the current setting)
5
6
End
2
Default interval
Data value