Panasonic FV-SWGR1 Installation And Operating Instructions Manual page 6

Remote control for energy recovery ventilator (erv)
Table of Contents

Advertisement

HOW TO INSTALL(RS485 CONNECTION)
2-1. Connect the wire
Low voltage connection (where the remote control is connected to the ERV): Refer to "1-1. Connect
the wire" in the section "How to Install".
Extra-low voltage connection(where the remote control is connected to RS485): Open the left back cover,
and refer to the figure below or the attached Wiring Diagram for details.
Wiring Stripping & Connection Diagram for RS485
(Correct)
Please use the general
RS485 cable.
6 mm
2-2. Disassemble the top cover
Refer to "1-2. Disassemble the Top Cover" in the section "How to Install".
2-3. RS485 Connection Settings
Terminal resistance setting
The terminal resistance of the RS485 unit is OFF by
default (as shown in figure on the right). Do not turn it
on if the wire connecting the product to the centralized
control system is less than 200 m; but turn it on if the wire is 200 m
or greater (Keeping it OFF may result in communication failure).
Notice
Terminal resistance: 120 Ω.
This value also applies to the relay.
To adjust the terminal resistance and machine
address, please use a small flat-head screwdriver.
Machine address setting
DIP SW 6 bits for setting the machine address.
By default, the address is set to 1. ( × : OFF ○ : ON)
Address
1
2
1
×
2
×
3
4
×
×
5
×
6
×
7
8
×
×
9
×
10
×
11
12
×
×
13
×
14
×
15
16
×
×
17
×
18
×
19
20
×
×
21
×
6
(Wrong)
The core wires are not
fully inserted into the
terminals.
List of the machine addresses
DIP SW
Address
3
4
5
6
22
×
×
×
×
23
×
×
×
×
24
×
×
×
×
25
×
×
×
26
×
×
×
27
×
×
×
28
×
×
×
29
×
×
×
30
×
×
×
31
×
×
×
32
×
×
×
33
×
×
34
×
×
35
×
×
36
×
×
37
×
×
×
38
×
×
×
39
×
×
×
40
×
×
×
41
×
×
42
×
×
Low voltage
connection
Extra-low voltage
connection
Notice
"A" indicates the positive end "﹢", while "B" the negative
end "﹣". Incorrect wiring will make control impossible.
Terminal
resistor
ON
*Write down the address set for future reference.
DIP SW
1
2
3
4
5
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
Terminal
resistor
OFF
DIP SW
Address
6
1
2
43
×
44
×
×
×
45
×
×
46
×
×
47
×
48
×
×
×
49
×
×
50
×
×
51
×
52
×
×
×
53
×
54
×
55
56
×
×
57
×
58
×
59
60
×
×
61
×
62
×
63
Centralized
control system
3
4
5
6
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×

Advertisement

Table of Contents
loading

Table of Contents