4-3. TEST RUN
*
Be sure to perform the test run for each unit. Make sure each indoor unit operates properly following the installation manual attached to the unit.
*
If you perform the test run for all indoor units at once, you cannot detect any erroneous connection, if any, of the refrigerant pipes and the indoor/outdoor
unit connecting wires.
About the restart protective mechanism
Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner.
4-4. EXPLANATION
TO THE USER
*
Using the OPERATING
INSTRUCTIONS,
explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air fil-
ters, how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.)
*
Recommend
the user to read the OPERATING
INSTRUCTIONS
carefully.
5. RELOCATION AND MAINTENANCE
5-1. PUMPING DOWN
When
relocating or disposing of the air conditioner, pump down the system following the procedure below so that refrigerant is not released into the atmos-
phere.
1) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.
2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when
the pressure gauge shows
0
MPa [Gauge] (0 Ibffin." [0 kgf/cm').
4) Start the emergency COOL
operation.
To start the emergency
operation
in COOL
mode,
disconnect the power supply plug and/or turn off the breaker. After 15 seconds,
connect the power
supply plug and/or turn on the breaker, and then press the E.O. SW once. (The emergency
COOL
operation can be performed continuously for up to 30
minutes.)
5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 7.25 to 0 Ibffin' [0.5 to 0
kgf/cm']).
6) Stop the emergency COOL operation.
To stop operation, press the E.O. SW several times until all LED lamps turn off. Refer to operating instructions for details.
A WARNING
When
pumping down the refrigerant, stop the compressor before disconnecting
the refrigerant pipes. The compressor may burst if air etc. get into it.