4-1-4 Setting an indoor unit installation option (suitable for the condition of each installation location)
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2. The panel(display ) should be connected to an indoor unit to receive option.
3. Set the installation option according to the installation condition of an air conditioner.
- The default setting of an indoor unit installation option is "02000-100000-200000-300000".
- Individual control of a remote controller(SEG20) is the function that controls an indoor unit individually when there is
more than one indoor unit.
- No need to assign SEG3, 6, 9, 10, 11, 16, 21, 22, 23, 24 which are non applicable. Even though those segments are set,
they will be ignored.
- If you set the applicable segments with numbers other than the indiciated, the initial setting will be maintained.
4. Set the indoor unit option by wireless remote controller.
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
Explanation
PAGE
Indication Details Indication Details
Indication
and
0
Details
Option
SEG7
Explanation
PAGE
Indication Details Indication Details
Indication
and
1
Details
Option
SEG13
Explanation
PAGE
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
Indication
and
2
Details
Samsung Electronics
SEG2
MODE
RESERVED
2
SEG8
Use of drain pump
RESERVED
0
Disuse
1
Use
Use +
2
3minute
delay
SEG14
SEG15
Use of external
Setting the output
control
of external control
0
Disuse
0
ON/OFF
1
Control
1
OFF
2
Control
SEG3
SEG4
Use of external
temperature sensor
Indication Details Indication Details
0
Disuse
1
Use
SEG9
SEG10
RESERVED
SEG16
S-Plasma ion
Thermo
0
Disuse
on
Operation
1
Use
on
SEG5
SEG6
Use of central
RPM setting
control
compensation
0. Not used
1. High ceiling mode
0
Disuse
2. High ceiling kit
3. Low noise operation mode
1
Use
SEG11
SEG12
Master / Slave
Indication Details
RESERVED
0
1
SEG17
SEG18
Number of hours
Buzzer control
using filter
0
Use of buzzer
2
Non use
1
6
of buzzer
slave
master
1000 Hour
2000
Hour
4-5