Fig. 46 - - Horizontal Left Application - - Vent Elbow Up
SEE NOTES: 1,2,4,5,7,8,9 on the page
following these figures
Fig. 47 - - Horizontal Left Application - - Vent Elbow Right
Caution!! For the following applications, use the minimum vertical heights as specified below.
FURNACE
ORIENTATION
Downflow
Horizontal Left
Horizontal Left
Horizontal Left
Downflow
Downflow
NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC.
*4 ---in. (102 mm) inside casing or vent guard
**Including 4 in. (102 mm) vent section(s)
A03215
A03216
For all other applications, follow exclusively the National Fuel Gas Code.
VENT ORIENTATION
Vent elbow left, then up
Fig. 37
110,000(036/--- 12 only)
Vent elbow right, then up
Fig. 40
Vent Elbow up
Fig. 41
Vent elbow right
Fig. 42
Vent elbow up then left
110,000 (036/--- 12 only)
Fig. 35
Vent elbow up, then right
110,000 (036/--- 12 only)
Fig. 38
SEE NOTES: 1,2,4,5,7,8,9 on the page
following these figures
Fig. 48 - - Horizontal Right Application - - Vent Elbow Left
Fig. 49 - - Horizontal Right Application- -Vent Elbow Left
MIN. VENT
FURNACE INPUT
DIAMETER
(BTUH/HR)
154,000 132,000
154,000 132,000
154,000 132,000
154,000
33
then Up
SEE NOTES: 1,2,4,5,7,8,9
MIN. VERTICAL VENT
HEIGHT
IN. (mm)*
FT. (M)**
5 (127)
12 (3.6)
5 (127)
7 (2.1)
5 (127)
7 (2.1)
5 (127)
7 (2.1)
5 (127)
10 (3.0)
5 (127)
10 (3.0)