Symptom: The Water At The Tap Is Too Cold; Symptom: Heat Pump Failure; Symptom: The System Is Making Gurgling Noises After Commissioning; Disposal - Daikin EBSH11P30D Operation Manual

Hide thumbs Also See for EBSH11P30D:
Table of Contents

Advertisement

Possible cause
The desired room temperature
cannot be reached.
The weather-dependent curve is
set incorrectly.
8.4
Symptom: The water at the tap is
too cold
Possible cause
You ran out of domestic hot
water because of unusually high
consumption.
The desired storage tank
temperature is too low.
8.5

Symptom: Heat pump failure

When the heat pump fails to operate, the backup heater or boiler can
serve as an emergency heater. It then takes over the heat load
either automatically or by manual interaction.
▪ When Emergency is set to Automatic and a heat pump failure
occurs, the backup heater or boiler automatically takes over the
domestic hot water production and space heating.
▪ When Emergency is set to Manual and a heat pump failure
occurs, the domestic hot water heating and space heating stops.
To manually recover it via the user interface, go to the
Malfunctioning main menu screen and confirm whether the
backup heater can take over the heat load or not.
▪ Alternatively, when Emergency is set to:
▪ auto
SH
reduced/DHW
domestic hot water is still available.
▪ auto SH reduced/DHW off, space heating is reduced and
domestic hot water is NOT available.
▪ auto
SH
normal/DHW
normally but domestic hot water is NOT available.
Similarly as in Manual mode, the unit can take the full load with
the backup heater or boiler if the user activates this via the
Malfunctioning main menu screen.
When the heat pump fails,
interface.
Possible cause
Heat pump is damaged.
INFORMATION
When the backup heater takes over the heat load,
electricity consumption will be considerably higher.
EBSH/X(B)11+16P30+50D
Daikin Altherma 3 R ECH₂O
4P663485-1C – 2023.05
Corrective action
Increase the desired leaving
water temperature in accordance
with the heat emitter type. See
"5.6.3 To change the desired
temperature" [ 4  12].
leaving water
Adjust the weather-dependent
curve. See
"5.9 Weather-
curve" [ 4  15].
dependent
Corrective action
If you immediately need domestic
hot water, activate the tank
Powerful operation. However,
this consumes extra energy. See
"5.7.3 Using DHW powerful
operation" [ 4  13].
If the problems recurs daily, do
one of the following:
▪ Adjust
the
storage
tank
temperature
schedule.
See
"5.8 
Schedule
screen:
Example" [ 4  13].
on, space heating is reduced but
off, space heating operates as
or
will appear on the user
Corrective action
See
"8.1 To display the help text
malfunction" [ 4  18].
in case of a
8.6
Symptom: The system is making
gurgling noises after
commissioning
Possible cause
There is air in the system.
Incorrect hydraulic balance.
Various malfunctions.
(a)
We recommend to purge air with the air purge function of the unit
(to be performed by the installer). If you purge air from the heat
emitters or collectors, mind the following:
WARNING
Air purging heat emitters or collectors. Before you
purge air from heat emitters or collectors, check if
is displayed on the home screen of the user interface.
▪ If not, you can purge air immediately.
▪ If yes, make sure that the room where you want to
purge air is sufficiently ventilated. Reason: Refrigerant
might leak into the water circuit, and subsequently into
the room when you purge air from the heat emitters or
collectors.
9

Disposal

NOTICE
Do NOT try to dismantle the system yourself: dismantling
of the system, treatment of the refrigerant, oil and other
parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for
reuse, recycling and recovery.
10

Glossary

DHW = Domestic hot water
Hot water used, in any type of building, for domestic
purposes.
LWT = Leaving water temperature
Water temperature at the water outlet of the unit.
9 Disposal
Corrective action
(a)
Purge air from the system.
To be performed by the installer:
1
Perform hydraulic balancing
to assure that the flow is
correctly
distributed
between the emitters.
2
If hydraulic balancing is not
sufficient, change the pump
limitation
settings
([9-0D]
and [9-0E] if applicable).
Check if
or
is displayed
on the home screen of the user
interface. See
"8.1 To display the
help text in case of a
malfunction" [ 4  18] for more
information about the
malfunction.
or
Operation manual