Startup & Adjustments; Pre-Start Check List; Start-Up Procedure; Air Circulation - Trane R8GD Series Installation Instructions Manual

Single package gas heating / electric cooling
Table of Contents

Advertisement

START UP & ADJUSTMENTS

Pre-Start Check List

√ Verify the unit is level and allows condensate to drain.
√ Verify all clearance requirements are met and there is
free airflow to and from the outdoor coil.
√ Verify that the duct work is sealed to prevent air leakage
and air filter is installed.
√ Verify that the line voltage power leads are securely
connected and the unit is properly grounded.
√ Verify that the low voltage wires are securely connected
to the correct terminals in the low voltage area of the
control box.
√ Verify that the gas line service pressure does not exceed
10.0 inches WC (0.36 psig), and is not less than 4.5
inches WC (0.16 psig) for natural gas. For LP gas the
line service pressure must not exceed 14 inches WC
(0.51 psig) and must not be less than 11.0 inches WC
(0.40 psig).
√ Verify that the flame roll-out control is closed. If
necessary, press the red button to reset the control. DO
NOT install a jumper wire across the control to defeat its
function. If the control reopens upon start-up, DO NOT
reset the control without identifying and correcting the
fault condition which caused the control to trip.
√ Verify that the gas line has been purged and all
connections are leak tight.
√ Verify that all exterior panels are replaced and securely
fastened.
√ Verify that the outdoor fan turns freely.
√ Verify that the power supply branch circuit overcurrent
protection is sized properly.
√ Verify that the thermostat is wired correctly. The
thermostat function switch should be set to OFF and
the thermostat fan switch should be set to AUTO.

Start-Up Procedure

WARNING:
If this unit is equipped with crankcase heaters,
allow 24 hrs for heating of the refrigerant
compressor crankcase prior to start up or
anytime the power has been removed for more
than 12 hrs. Failure to comply may result in
damage or cause premature failure of the
system.

Air Circulation

Leave the thermostat system mode on OFF, and set the
fan mode to ON. Blower should run continuously. Check
the air delivery at the supply registers and adjust register
openings for balanced air distribution. Examine ductwork
for leaks or obstruction if insufficient air is detected. Set
the thermostat fan mode to AUTO. The blower should
stop running.
16

System Cooling

1. Set the thermostat's system mode to COOL and the
fan mode to AUTO. Gradually lower the thermostat
temperature setpoint below room temperature and verify
the compressor, fan and indoor blower energize.
2. Feel the air being circulated by the indoor blower and
verify that it is cooler than ambient temperature. Listen for
any unusual noises. If unusual sounds occur, determine
the source of the noise and correct as necessary.
3. Allow the cooling system to operate for several minutes
and then set the temperature selector above room
temperature. Verify the fan and compressor cycle off
with the thermostat. NOTE: The blower will also stop
after a 40 second delay.

System Heating

1. Set the thermostat to the lowest setting.
2. Follow the procedures given on the operating instruction
label, this manual or attached inside the louvered control
access panel.
3. Set the thermostat above room temperature and verify
the Operating Sequence. See page 18.
4. Verify that the compressor and outdoor fan motor are
not energized.
5. After the unit has run for approximately five minutes,
set the thermostat below room temperature and verify
the shutdown sequence; steps 10 -12 in the Operating
Sequence section (pages 18-19).
Verifying & Adjusting Temperature Rise
Verify the temperature rise through the unit is within the
range specified on the unit data label. Temperature rises
outside the specified range could result in premature heat
exchanger failure.
1. Place thermometers in the return and supply air stream
as close to the unit as possible. The thermometer on the
supply air side must be shielded against direct radiation
from the heat exchanger to avoid false readings.
2. Adjust all registers and duct dampers to the desired
position. Run the unit for 10 to 15 minutes before
taking any temperature readings. The temperature
rise is the difference between the supply and return air
temperatures.
NOTE: For typical duct systems, the temperature rise will
fall within the range specified on the data label (with the
blower speed at the factory recommended setting) shown
in Table 8 (page 23). If the measured temperature rise falls
outside the specified range, it may be necessary to change
the blower speed. Lowering the blower speed increases
the temperature rise and a higher speed decreases the
temperature rise.
The unit is equipped with a multi speed motor. On units
with ECM type motors, speed selection is made by moving
the leads on the blower motor terminal block. If the unit
is equipped with a PSC type motor, speed selection is
made by moving the leads on the furnace control board.
The speed taps for adjusting the motor speed are shown
in the unit wiring diagram or Figures 11 & 12 (pages 27
& 28). Refer to the Blower Speed section (page12) for
additional information.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ppg3gd series

Table of Contents