Fujitsu AO G22KBTB Series Service Manual page 69

Split type room air conditioner
Hide thumbs Also See for AO G22KBTB Series:
Table of Contents

Advertisement

SERVICE PARTS INFORMATION 2
Inverter Compressor
Check Point 1 : Check Connection
Check terminal connection of Compressor
(loose or incorrect wiring)
Check Point 2 : Check Winding Resistance
Check winding resistance of each terminal
If the resistance value is 0
U
W
Check Point 3 : Replace Main PCB
If the symptom does not change with above Check 1, 2, replace Main PCB.
Terminal cover opened
W(C)
U(R)
(BLACK)
(RED)
V(S)
(WHITE)
or infinite, replace Compressor.
Resistance Value :
V
Main PCB
RED
1.91
at 20°C
02-38
W400 W401 W402
Compressor
BLACK
WHITE