ELECTRICAL CONNECTIONS
7
ELECTRICAL CONNECTION
REQUIREMENTS
This appliance must be installed and grounded
ona
branch circuit by a qualified technician in accordance
with the National Electrical code ANSI/NFPA NO. 70 -
latest edition.
All wiring should conform to Local and NEC. This range
requires a single-phase, 3 wire, A.C 120/208V or 120/240V
60Hz electrical system. Use only a 3-conductor ora
4-conductor UL-listed range cord with closed-loop
terminals, open-end
spade lugs with upturned ends
or similar termination. DO NOT install the power cord
without a strain relief.
A range cord rated at 40 amps with 120/240 minimum
volt range is required. If a 50 amp range cord is used, it
should be marked for use with 138" diameter connection
openings. This appliance may be connected by means
of conduit or power cord. If conduit is being used, go to
page 7 for 3 wire conduit connections or page 8 for 4
wire conduit connections.
4, WARNING
« New branch-circuit installations (1996 NEC)
for mobile homes, recreational vehicles, and
installations where local codes do not allow
grounding through the neutral wire require
a 4-conductor UL listed range cord or 4 wire
conduit connection.
« Power supply cord and plug should not be
modified. if it will not fit the outlet, have a
proper outlet Installed by a qualified electrician.
« Using an extension cord to connect the power is
prohibited. The way to connect the power cord
and plug directly is strongly recommended.
« Electrical ground is required on this appliance.
« You should make sure that the power cord is
not pinched by the range or heavy objects.
- Failure to do so can result in serious burns or
electrical shock.
Specified power-supply-cord kit rating
Range rating, watts
Specified
Diameter (inches) of Range
rating of power
connection Opening
120/240 volts | 120/208 volts | supply-cord kit,|
Power cord
Conduit
3-wire
3-wire
amperes
8,750- 16,500 | 7,801- 12,500 |
40 or50A
13/3"
11/3"
16,501 - 22,500) 12,501 - 18,500
50
13/4"
13/3"
3, 4- Wire electrical wall Receptacle
4 Wire receptacle (14-50R)
|
| Q
3 Wire receptacle (10-50R)
|
Flg URE 3
CONNECT
RANGE CORD
The Rear Access cover must be removed. Loosen the
three screws with a screwdriver. The terminal block will
then be accessible.
Cord/Conduit
Access
connection
cover
Drawer body
plate
FIgURE 4
The Cord/Conduit connection
plate is used for the
installation of power cord or conduit. For power cord,
install it with the connection plate as INSTALLED. For
conduit, remove the connection plate located below the
rear of the drawer body and use the conduit hole (1 1/3")
instead of power cord hole (1 3/8"). (Refer to Figure 5 and 6.)
V/s"
ck 8cm)
——==
P/s"
P/s"(Cord) — 1'/e" (Conduit)
(3.5em)
Remove the Conduit connection plate
FIgURE 5
Cord/conduit
connection
Strain relief
Conduit
Assemble the
strain relief hole
Cord Strain
"4
relief
~
Reinstall the Cord/Conduit connection plate
FIgURE 6