11-6. HOW TO CHECK THE PARTS
PUZ-HA30NHA
PUZ-HA36NHA
Parts name
Thermistor (TH3)
Disconnect the connector then measure the resistance with a tester.
<Outdoor pipe>
(Ambient temperature 10 ~30 , 50°F~86°F)
Thermistor (TH4)
<Discharge>
Thermistor (TH6)
<Outdoor 2-phase pipe>
Thermistor (TH7)
<Outdoor>
Thermistor (TH8)
<Heatsink>
Thermistor (TH32)
<Outdoor pipe>
Thermistor (TH33)
<Outdoor pipe>
Fan motor(MF1,MF2)
Refer to next page.
Solenoid valve coil
Measure the resistance between the terminals with a tester.
(Ambient temperature 20 , 68°F)
<Four-way valve>
(21S4)
Motor for compressor
Measure the resistance between the terminals with a tester.
(Winding temperature 20 , 68°F)
(MC)
U
V
W
Linear expansion valve
Disconnect the connector then measure the resistance with a tester.
(LEV-A/LEV-B/LEV-C)
(Winding temperature 20 , 68°F)
Gray
M
1
2
Orange
3
Red
4
Yellow
5
Black
6
Measure the resistance between the terminals with a tester.
Solenoid valve coil
(Ambient temperature 20 , 68°F)
<Bypass valve>
(SV)
PUZ-HA30NHA2
Normal
TH4
160k ~410k
TH3
TH6
TH7
4.3k ~9.6k
TH32
TH33
TH8
39k ~105k
Normal
1435
150
Normal
0.188
Gray - Black
Gray - Red
Normal
1197
10
PUZ-HA36NHA2
Check points
Abnormal
Open or short
Abnormal
Open or short
Abnormal
Open or short
Normal
Gray - Yellow
Gray - Orange
46
3
Abnormal
Open or short
46
Abnormal
Open or short