INSTALLATION

Read completely, then follow step by step.

Selection of the best location

There should not be any heat source or steam near the unit.
There should not be any obstacles to the air circulation.
A place where air circulation in the room will be good.
A place where drainage can be easily obtained.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
The indoor unit must have the maintenance space.
Ceiling
Ceiling board
≥ 1,500(59-1/16)*
NOTE
!
* : Minimum Installation Space to Air flow direction A separation distance of at least
1,500 mm is required throughout the airflow direction.
** : A, Installation Height from the floor
Capacity Class
< 10 kW
≥ 10 kW
*** : Minimum Height
In case the applied refrigerant is R32, the installation height must be 2.2m or more.
Exact details follow IEC regulations.
**** : Standard Height (Recommended)
If it exceeds the standard height, set the 'High Ceiling Mode'.
For details about function setting, refer to the installation manual.
Floor
Installation Height (A)
Min.***
Standard ****
2.0 m (6.56 ft)
2.7 m (8.86 ft)
2.5 m (8.20 ft)
3.2 m (10.50 ft)
INSTALLATION
[Unit:mm(inch)]
Ceiling board
≥ 1,500(59-1/16) *
3.6 m (11.81 ft)
4.2 m (13.78 ft)
13
Max.