Toshiba TOSVERT VF-A3 Instruction Manual page 78

High performance inverter
Hide thumbs Also See for TOSVERT VF-A3:
Table of Contents

Advertisement

5)
Set to the following data, refer to a block diagram Figure 3.31
Data and setting range
Standard value
Parameter
Calculation
Adjustment range
Parameter value
Setting data
Proportional gain
Gp
GP
0-39
GP:
0 -
9999
Gp=l
GP=256
256
r,
Integral gain
GI
_U_'_
0-39
Gt :
0 -
9999
GI=0.18
GI =46
255
Antihunting gain
GA
GR
0-1
CR:
0 -
255
GA=O
CR=O
256
Temporary delay
filter constant
GFS
GFS
o -
255
CFS
: 0-
255
GFS=15
CFS=15
• Set the data as follows.
[Example] When you set the proportional gain Gp to
1,
set the data
GP
as follows.
GP
= Gp
x
256
=
256
• For details of setting procedure, refer to Section 3.1.2 (page
23). Its function number is 5.
process rate
fref
e
feedback rat
fF.B.
+
-
-
Gp
+
GI
+
+
GFS
S
-
-
S
GA
Figure 3.31
Block diagram
6)
An acceleration and deceleration time must be set as short as possible.
Outpu
t
f
7)
When you want to limit an output, set upper and lower limit frequency (refer to page 82).
8)
Start or Stop a run via the inverter's operating panel or by switching ON or OFF between F and
CC terminals. Check the command mode, refer to Section 3.23 (page 73). To reset the
integral value by pushing the STOP key on the inverter's operating panel or by switching OFF
between F and CC terminals.
9)
Figure 3.32 shows the pressure constant control as an example.