Time Delay Module (Tdm) For Uvr (Externally Mounted); Remote Operation Coil Combination; Auxiliary Switches - GE EntelliGuard G Installation, Operation And Maintenance Manual

Hide thumbs Also See for EntelliGuard G:
Table of Contents

Advertisement

DEH-41304C
13 March 14
Table 6.5. UVR Operating Characteristics
Power
Nominal Control
Consumption
Voltage
24/30 Vdc
DC: 350 W,
40 Vdc; 48 Vac/dc
20 W (sealed)
60 Vdc
110/130/120 Vac
AC: 350 W
208 Vac
(inrush),
220 Vdc/240 Vac
20 W (sealed)
250 Vdc/277 Vac
 Duty cycle = 2/min.
 Inrush = 350 VA (ac), 350 W (dc).
 Holding = 60 VA (ac), 50 W (dc).

Time Delay Module (TDM) for UVR (Externally Mounted)

The de-energized operation of the Under Voltage release can
be delayed. This optional, externally mounted module has an
adjustable time delay of 0 s to 3 s. The device can be
implemented to prevent undesired breaker tripping due to
momentary voltage interruptions and is connected in series
with the Under Voltage release. The time delay is in addition
to the time delay from the breaker mounted UVR accessory.
The time delay module starts counting at 50% of rated
voltage (Fig. 6.2 and Table 6.6).
Figure 6.2. Time Delay Module
Table 6.6 TDM Characteristics
Nominal Control Voltage
48VDC
48VAC
60VDC
120VDC
120VAC
208VAC
240VDC
240VAC
250VDC
277VAC
©2012 General Electric All Rights Reserved
Courtesy of store.ips.us

Remote Operation Coil Combination

Each breaker accepts a maximum of four coils in the
combinations shown in Table 6.7. All coils are mounted from
Catalog
the front and snap onto the mechanism after the fascia is
Number
removed.
GUVT030DR
GUVT048R
Table 6.7. Remote Operation Coil Combination
GUVTO60DR
Combination
GUVT130R
GUVT208AR
GUVT240R
GUVT277R

Auxiliary Switches

Auxiliary switches indicate breaker main contact position.
They change their state in the same time sequence as the
breaker main contacts. See Tables 6.8 and 6.9 for available
combinations and ratings.
Table 6.8. Auxiliary Switches
Contact Configuration
Power rated (3NO+3NC)
Power rated (3NO+3NC) + low signal (Hi-Fi)
(2NO+2NC)
Power rated (8NO+8NC)
Power rated (4NO+4NC) + low signal (Hi-Fi)
(4NO+4NC)
Table 6.9. Auxiliary Switch Ratings and Secondary
Disconnect Points
Contact Configuration
Power rated
(3NO+3NC)
Power rated (3NO+3NC) +
low signal (Hi-Fi)
(2NO+2NC)
Power rated
(8NO+8NC)*
Catalog No.
GTDM048D
Power rated (4NO+4NC) +
GTDM048A
low signal (Hi-Fi)
GTDM060D
(4NO+4NC)*
GTDM120D
*Options are not available for side mounted sec disc blocks.
GTDM120A
 High Fidelity refers to gold-plated contacts. Use for signal level outputs
GTDM208A
(10 mA min to 100 mA max., 8 Vdc to 30 Vdc, 125 Vac.
GTDM240D
GTDM240A
GTDM250D
GTDM277A
EntelliGuard® G Circuit Breaker
Section 6 – Accessories Description
Coil Position on Fascia (from left)
1
2
1
-
shunt
2
shunt
shunt
3
shunt
UV
Power
Rated
A14 - A25
A14 - A25
A14 - A25,
B4 - B13,
B17 - B26
A14 - A25,
B12 - B13,
B25 - B26
3
4
CC
UV
CC
UV
CC
UV
Cat. No.
GAUX3R
GAUX5R
GAUX6R
GAUX8R
Hi-Fi
Cat. No.
N/A
GAUX3R
B10 - B13,
GAUX5R
B23 - B26
N/A
GAUX6R
B4 - B11,
GAUX8R
B17 - B24
29